Technical Data - Vents VUTR 280 V EC User Manual

Heat recovery air handling unit
Table of Contents

Advertisement

The unit is designed for indoor application with the ambient temperature ranging from +1 °C (+33.8 °F) up to +40 °C (+104 °F) and relative
humidity up to 80 %.
In order to prevent condensation on the internal walls of the units, it is necessary that the surface temperature of the casing is 2-3 °C higher
than the dew point temperature of the transported air.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Maximum unit power (without a heater) [W]
Maximum unit power (with a heater) [W]
Maximum unit current (without a heater) [A]
Maximum unit current (with a heater) [A]
Sound pressure level at 3 m distance [dBA]
Maximum transported air temperature [°C]
www.ventilation-system.com
Parameter
Unit voltage [V/50 (60) Hz]
Maximum heater power [W]
Maximum heater current [A]
Maximum air flow [m
Casing material
Filter:
Connected air duct diameter [mm]
Weight [kg]
Heat recovery efficiency [%]
Heat exchanger type
Heat exchanger material

TECHNICAL DATA

VUTR 280 V EC
3
/h]
RPM, min-
1
Insulation
extract
supply
SEC class
TECHNICAL DATA
1~ 230
195
195
1.9
-
1.9
300
2050
26
from -25 up to +40
painted steel
40 mm mineral wool
G4
F7
125
63
from 81 up to 90
rotary
aluminium
А
VUTR 280 VE EC
650
845
2.8
4.7
64
5