NIVELCO THERMOPOINT TM-500 User And Programming Manual

NIVELCO THERMOPOINT TM-500 User And Programming Manual

Multipoint temperature transmitters

Advertisement

Quick Links

THERMOPOINT
TM / J-500 / 600
Multipoint temperature transmitters
Manufacturer:
NIVELCO Process Control Co.
H-1043 Budapest, Dugonics u. 11.
Phone: (36-1) 889-0100
Fax: (36-1) 889-0200
E-mail:
sales
@nivelco.com
www.nivelco.com

Advertisement

Table of Contents
loading

Summary of Contents for NIVELCO THERMOPOINT TM-500

  • Page 1 THERMOPOINT TM / J-500 / 600 Multipoint temperature transmitters Manufacturer: NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Phone: (36-1) 889-0100 Fax: (36-1) 889-0200 E-mail: sales @nivelco.com www.nivelco.com...
  • Page 2 2 / 28 ♦ BKI 10 ATEX 0003 X ♦ BKI 11 ATEX 0016 X ♦ tmh5554a0600p_03.doc...
  • Page 3: Table Of Contents

    CONTENTS 5.3.2. Analogue output ....................18 1. INTRODUCTION....................5 5.3.2.1 Output current mode................18 1.1. A PPLICATION .................... 5 5.3.2.2 Output current value 4mA..............18 2. ORDER CODES....................6 5.3.2.3 Output current value 20mA..............18 3. TECHNICAL DATA..................7 5.3.2.4 Output current error mode..............19 3.1.
  • Page 4 4 / 28 ♦ BKI 10 ATEX 0003 X ♦ BKI 11 ATEX 0016 X ♦ tmh5554a0600p_03.doc...
  • Page 5: Introduction

    Thank you for choosing a NIVELCO instrument. We are sure that you will be satisfied throughout its use! 1. INTRODUCTION 1.1. A PPLICATION THERMOPOINT TM/J-500/600 series two-wire temperature transmitters are suitable for continuous multipoint temperature-measurement, -indication and -transmission of normal and hazardous liquids, powders or granular solids. The sensor of the instrument is located in a rigid or flexible stainless steel tube, or an antistatic plastic coated steel tube depending on the measured material and the insertion length.
  • Page 6: Order Codes

    2. ORDER CODES Not all combinations possible! THERMOPOINT multipoint temperature transmitters: ROBE UMBER OF OUSING ENGTH UTPUT ROCESS CONNECTION SENSORS Multipoint transmitter Rod 1” NPT Aluminium HART Rod M20x1,5 Plastic HART / Ex iaD Multipoint transmitter + display Cable 1 ½ ” BSP HART / Ex ia Cable 1 ½”...
  • Page 7: Technical Data

    3. TECHNICAL DATA 3.1. G ENERAL DATA IGID TUBE VERSION LEXIBLE TUBE VERSION LEXIBLE PLASTIC COATED TUBE VERSION Type T R- - , T A- T K- - , T E- T H- - , T C- T J- Nominal length 0.5 m …...
  • Page 8: Additional Data Fore X Approved Models

    3.2. A DDITIONAL DATA FOR X APPROVED MODELS T R-5 -6 E T R-6 -6 E T K-5 -6 E T K-6 -6 E T H-5 -5 E T H-5 -8 E Type T A-5 -6 E T A-6 -6 E T E-5 -6 E T E-6...
  • Page 9: Dimensions

    3.3. D IMENSIONS OR SOLIDS OR LIQUIDS OSITION OF SENSORS IN STANDARD VERSION T R- , T A- T H- , T C- T K- , T E- T J- 1 1/2" BSP 1 1/2" BSP 1" BSP 1 1/2" NPT 1 1/2"...
  • Page 10: Accessories

    3.4. A CCESSORIES User’s and programming manual, Warranty Card, Declaration of Conformity, 2 pcs M20x1.5 cable gland. 4. INSTALLATION AND WIRING During the installation the following instructions should be taken into consideration: Depending on the thermal characteristics of the measured material the sensor should be installed proper distance from the silo wall, Depending on the cross section of the silo several sensors should be installed, In case of temperature measurement of granular solids static data of the silo roof should be checked and if necessary proper mechanical solution should be performed to relieve the roof.
  • Page 11: Wiring

    4.1. W IRING The transmitter is designed to operate in 2-wire systems with 12…30 V DC power supply Display unit connector voltage. Resistance of the units in the loop current depends on the applied supply voltage. Shielded cable should be used for wiring. RELAY Screw terminals can be accessed after removing the housing cover and the display module (if there is).
  • Page 12: Putting Into Operation, Programming

    The SAP-300 is a 64x128 dot-matrix LCD display which can be plugged into the transmitter. (Universal – usable in other NIVELCO devices as well – provided that the system software supports SAP-300.) Warning! The SAP-300 module is based on LCD technology, so please make sure it is not exposed to permanent heat or direct sunlight, in order to avoid damage of the display unit.
  • Page 13: Measuring With The Sap-300 Display Module

    5.1. M SAP-300 D EASURING WITH THE ISPLAY MODULE Elements of the display: 1, Measured temperature values. According to the increasing number from the top to the bottom and from left to right. Instrument can operate with maximum 15 sensors. 6 horizontal lines indicate the lack or the error of the sensor. The #1 sensor is the closest to the electronic housing, the following sensors are tagged with the next numbers increasingly.
  • Page 14 Information displays Press button to cycle between the information displays. 1. The general information display (DEV. INFO): overall running time (OV. RUN TIME), run time after power on (RUN TIME), type of interface (INTERFACE). 2. Sensor information: number of the temperature sensors in the probe (TOTAL SENSOR COUNT), number of the highest numbered sensor (RANGE).
  • Page 15: Programming With The Sap-300 Display Module

    5.2. P SAP-300 ROGRAMMING WITH THE DISPLAY MODULE When entering the menu the instrument makes a copy of the actual parameters, all changes are done to this duplicated parameter set. During programming the instrument keeps measuring and transmitting with the current (and intact) parameter set. After exiting the menu the instrument replaces the original parameters with the new parameter set and will measure according to the new parameters.
  • Page 16: Menu Structure

    Dialog window The system sends messages or warnings using dialog windows. These usually can be acknowledged by pressing the button or the user can choose between two options (usually YES or NO) by pressing buttons. In some cases to correct an error one of the parameters has to be changed! Edit window An edit window is used for modifying a numeric parameter value.
  • Page 17: Programmable Features Description

    5.3. P ROGRAMMABLE FEATURES DESCRIPTION 5.3.1. Basic measurement settings 5.3.1.1 Source of transmitted PV (Primary Value) Parameter: P01: a Menu path: BASIC SETUP / PRIMARY VALUE Default value: AVERAGE Description: The selected value will be the base of the analogue and the digital (HART) transmitted Primary Value. AVERAGE SELECTED SENSOR MAXIMUM...
  • Page 18: Analogue Output

    5.3.2. Analogue output 5.3.2.1 Output current mode Parameter: P12: b Menu path: OUTPUT SETUP / ANALOG OUTPUT / CURRENT MODE Default value: AUTO Description: Transmission mode of the current output [AUTO, MANUAL] AUTO The output current is calculated from the Primary Value (P01: a), output is active. MANUAL The output current is fixed at a constant (set) value.
  • Page 19: Output Current Error Mode

    5.3.2.4 Output current error mode Parameter: P12: a Menu path: OUTPUT SETUP / ANALOG OUTPUT / ERROR MODE Default value: 22mA Description: Error indication on the current output: Error indication is OFF. The device transmits in accordance to the last calculation. 3.8 mA In case of error, the output current gets 3.8 mA.
  • Page 20: Service Functions

    5.3.4. Service functions 5.3.4.1 Security codes User security code Parameter: Menu path: SERVICE / SECURITY / USER LOCK Description: Setting or unlocking the user security code. The instrument can be protected against unauthorized programming with a 4 digit PIN (Personal Identification Number) code. If either of the digits differs from 0 the code is active.
  • Page 21: Temperature Simulation

    5.3.4.3 Temperature simulation This function helps the user to check the outputs and the connected processing units After finishing of the settings the unit should be returned into Measurement mode to start the simulation. Temperature simulation mode Parameter: P84: a Menu path: SERVICE / PV SIMULATION / MODE Default value:...
  • Page 22: Load Default Values

    Upper value of the Temperature simulation Parameter: Menu path: SERVICE / PV SIMULATION / UPPER VALUE Default value: 85 ºC Description: Highest value of the simulation 5.3.4.4 Load default values Parameter: Menu path: SERVICE / DEFAULTS / LOAD DEFAULT Description: This command loads all default values of the instrument.
  • Page 23: Error Codes

    5.4. E RROR CODES Message on the screen Error description Procedure MEMORY ERROR Memory error in the electronics Contact the service! NO INPUT SIGNAL Hardware error Contact the service! EE COM. ERROR Hardware error Contact the service! MATH. OVERLOAD Display overflow Check the programming! SENSOR NOT FOUND Hardware error...
  • Page 24: Communication Via Multi Cont Process Controller

    5.5. RS485 CONT COMMUNICATION VIA ULTI PROCESS CONTROLLER 5.5.1. Remote programming with HART protocol Knowing the HART commands of the transmitters, with the help of USER RS485 interface of MultiCONT process controller (this case MultiCONT acts as a bridge) there is a possibility to perform remote programming of the connected transmitters. This can be done the following way: the MASTER inserts the HART frame to the data field of the HART frame, which is sent by the MultiCONT to the transmitters the MultiCONT „unpack”...
  • Page 25: Remote Programming With Modbus Protocol

    5.5.2. Remote programming with MODBUS protocol Knowing the HART commands of the transmitters, with the help of USER RS485 interface of MultiCONT process controller (this case MultiCONT acts as a bridge) there is a possibility to perform remote programming of the connected transmitters. This can be done the following way: the MASTER inserts the HART frame to the data field of the MODBUS frame, which is sent by the MultiCONT to the transmitters the MultiCONT „unpack”...
  • Page 26: Maintenance And Repair

    -25 ºC …+60 ºC Relative humidity: max. 98% 8. WARRANTY NIVELCO provides warranty of 3 (three) years in compliance with details described in the Warranty Card. 26 / 28 ♦ BKI 10 ATEX 0003 X ♦ BKI 11 ATEX 0016 X ♦ tmh5554a0600p_03.doc...
  • Page 27: Menu Map

    9. MENU MAP BKI 10 ATEX 0003 X ♦ BKI 11 ATEX 0016 X ♦ tmh5554a0600p_03.doc ♦ 27 / 28...
  • Page 28 September 2012. Nivelco reserves the right to change technical specifications without notice. 28 / 28 ♦ BKI 10 ATEX 0003 X ♦ BKI 11 ATEX 0016 X ♦ tmh5554a0600p_03.doc...

This manual is also suitable for:

Thermopoint tj-500Thermopoint tj-600Thermopoint tm-600

Table of Contents