Wireless single-phase current detection sensor
Hide thumbs Also See for R718N1:

Advertisement

5. Data Report

When the device is turned on, it will immediately send a version package and a cluster report which
Includes current values (mA).
Data will be reported once every 30 minutes by default setting.
Maximum time: Max Interval
Minimum time: Min Interval (Check the current voltage once per Min Interval)
Default reportchange:
Current----0x0064 (100mA)
Note:
The data transmission period of the device is subject to the programming configuration. If the minimum time of report configuration is less than 30
seconds, all counted for 30 seconds. If the the maximum time of report configuration is less than minimum time, all counted for minimum time.
The device starts sampling 15 seconds before the minimum time is due, and lasts for 15 seconds. If the current changes frequently, the sampling result
may be inaccurate. Press function key to trigger.
For the analysis of the data reported by the device,
refer to the Netvox LoraWAN Application Command document and http://www.netvox.com.cn:8888/page/index.
Data report configuration and sending period are as following:
Min. Interval
Max. Interval
(Unit:second)
(Unit:second)
Any
Any
number
between
between 30~65535
Min.~65535
Uplink report payload example:
1
1
1
Version
DeviceT
ReportTyp
ype
e
0x01
0x49
0x01
Uplink example:
0149012403E80100000000
The battery voltage is 3.6V, the single-phase current is 1000mA, and the multiplier is 1.
Report configuration:
Description
CmdID
Device
ConfigRepo
0x01
rtReq
ConfigRepo
0x81
rtRsp
R718N1
ReadConfig
0x02
ReportReq
ReadConfig
0x82
ReportRsp
Reportable Change
number
Can not be 0.
Battery(1Byte,
Current(2Bytes,Un
unit:0.1V)
it:1ma)
Device
Type
MinTime(2bytes Unit:s)
Status(0x00_success)
0x49
MinTime(2bytes Unit:s)
Current Change≥ Reportable
Current Change<Reportable Change
Change
Report
Report
per Min. Interval
per Max. Interval
Var(Fix=8 Bytes)
NetvoxPayLoadData
Multiplier(1Byte),the real
current should convert with
Current* Multiplier
NetvoxPayLoadData
CurrentChange(2byte
MaxTime(2bytes Unit:s)
Reserved (8Bytes,Fixed 0x00)
Reserved (9Bytes,Fixed 0x00)
CurrentChange(2byte
MaxTime(2bytes Unit:s)
4
Reserved(4Bytes,fixed 0x00)
Reserved
Unit:1mA)
(3Bytes,Fixed
0x00)
Reserved
Unit:1mA)
(3Bytes,Fixed
0x00)