netvox R718UBB Series User Manual

netvox R718UBB Series User Manual

Wireless multifunctional co2 sensor

Advertisement

Quick Links

R718UBB Series
Wireless Multifunctional CO2 Sensor
Wireless Multifunctional
CO2 Sensor
R718UBB Series
User Manual
Copyright©Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be
maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written
permission of NETVOX Technology. The specifications are subject to change without prior notice.

Advertisement

Table of Contents
loading

Summary of Contents for netvox R718UBB Series

  • Page 1 User Manual Copyright©Netvox Technology Co., Ltd. This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written...
  • Page 2: Table Of Contents

    Table of Content 1. Introduction .......................... 2 2. Appearance ........................... 3 3. Main Feature ........................3 4. Set up Instruction ......................... 4 5. Data Report .......................... 5 5.1 Example of ReportDataCmd ..................6 5.2 Example of ConfigureCmd .................... 7 5.3 Example of calibration configuration ................9 6.
  • Page 3: Introduction

    1. Introduction R718UBB all-in-one series is a ClassA type testing device based on LoRaWAN open protocol of Netvox, which can support multiple combinations of temperature and humidity, CO2, vibration, atmospheric pressure and illumination sensors, and is compatible with LoRaWAN protocol.
  • Page 4: Appearance

     Low power consumption and long battery life Note: Battery life is determined by the sensor reporting frequency and other variables, please refer to http://www.netvox.com.tw/electric/electric_calc.html. On this website, users can find battery life time for varied models at different configurations.
  • Page 5: Set Up Instruction

    4. Set up Instruction On/Off Power on Insert batteries. (users may need a screwdriver to open) Turn on Press and hold the function key for 3 seconds till the green indicator flashes once. Turn off (Restore to factory setting) Press and hold the function key for 5 seconds till green indicator flashes 20 times. Power off Remove Batteries.
  • Page 6: Data Report

    If the CO2 value which customers test is inconsistent ,or there is large discrepancy of the primary standard, it can be recalibrated. For specific calibration methods,please refer to command 0x03 CalibrateType. Refer to Netvox LoRaWan Application Command documents and for data analysis reported by the device http://www.netvox.com.cn:8888/page/index...
  • Page 7: Example Of Reportdatacmd

    Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version DeviceType– 1 byte – Device Type of Device The devicetype is listed in Netvox LoRaWAN Application Devicetype doc ReportType – 1 byte –the presentation of the NetvoxPayLoadData,according the devicetype NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
  • Page 8: Example Of Configurecmd

    5.2 Example of ConfigureCmd FPort:0x07 Bytes Var (Fix =9 Bytes) CmdID DeviceType NetvoxPayLoadData CmdID– 1 byte DeviceType– 1 byte – Device Type of Device NetvoxPayLoadData– var bytes (Max=9bytes) MinTime MaxTime Reserved ConfigReportReq 0x01 (2bytes Unit:s) (2bytes Unit:s) (2Bytes,Fixed 0x00) Status Reserved ConfigReportRsp 0x81...
  • Page 9 (1) Configure the device parameter MinTime = 300s, MaxTime = 900s Downlink: 01BB012C03840000000000 Device return: 81BB000000000000000000 (configuration successful) 81BB010000000000000000 (configuration failed) (2) Read the device parameter Downlink: 02BB000000000000000000 Device Return: 82BB012C03840000000000 (device current parameter) (3) Set CO2 calibration Downlink: 03BB0103E8000000000000 // Select Target-calibrations (calibrate when the known CO2 concentration is 1000ppm (concentration optional)) 03BB020000000000000000...
  • Page 10: Example Of Calibration Configuration

    5.3 Example of calibration configuration FPort:0x0E Sensor Description CmdID PayLoad(Fix =9 Bytes) Type SetGlobal Channel (1Byte) Multiplier Divisor DeltValue Reserved 0x01 0_Channel1 CalibrateReq (2bytes,Unsigned) (2bytes,Unsigned) (2bytes,Signed) (2Bytes,Fixed 0x00) 1_Channel2,etc Channel (1Byte) SetGlobal Status Reserved 0x81 0_Channel1 CalibrateRsp (1Byte,0x00_success) (7Bytes,Fixed 0x00) 1_Channel2,etc below Channel (1Byte)
  • Page 11: Information About Battery Passivation

    Device return:8300000000000000000000 6. Information about Battery Passivation Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density. However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high.
  • Page 12: Precautions For Outdoor Installation

    Brand Load Resistance Activation Time Activation Current 165 Ω NHTONE 5 minutes 20mA 67 Ω RAMWAY 8 minutes 50mA 67 Ω 8 minutes 50mA 67 Ω SAFT 8 minutes 50mA Note: If you buy batteries from other than the above four manufacturers, then the battery activation time, activation current, and required load resistance shall be mainly subject to the announcement of each manufacturer.
  • Page 13: Important Maintenance Instruction

    8. Important Maintenance Instruction Kindly pay attention to the following in order to achieve the best maintenance of the product: • Keep the device dry. Rain, moisture and various liquids or water may contain minerals that can corrode electronic circuits. In case the device is wet, please dry it completely.