Optically Isolated Differential Inputs; Sensing Dc Voltages - National Instruments NI 6520 User Manual

Contains five form a single-pole single-throw (spst) non-latching relay outputs, three form c single-pole double-throw (spdt) non-latching relay outputs, and eight channel-to-channel isolated industrial inputs
Hide thumbs Also See for NI 6520:
Table of Contents

Advertisement

Pin
12, 30, 14, 32, 16, 34, 18,
36
13, 31, 15, 33, 17, 35, 19,
37

Optically Isolated Differential Inputs

© National Instruments Corporation
Table 3. NI 6520/6521 Signal Descriptions (Continued)
Signal Name
P0.<7..0>+
P0.<7..0>–
The input lines on the NI 6520/6521 device provide 8 lines of optically
isolated digital input. These inputs contain an AC input photocoupler and a
resistor for current limiting. The maximum input voltage (VIN) on these
lines is 30 VDC.
The input (VIN) range on the channels is –30 VDC to
(NI 6520 Only)
+30 VDC, for signals connected between P0.X+ to P0.X–, where X is
line <0..7>.

Sensing DC Voltages

The NI 6520/6521 can sense DC signals from 11 V to DC power supply
levels up to 30 V.
Input voltages between –4 V to +4 V produce a logic low. Input voltages
between –30 V to –11 V or between +11 V to +30 V produce a logic high.
The logic state of signals between –11 V to –4 V and +4 V to +11 V is not
defined. This corresponds to standard industrial 24 V logic thresholds.
There should never be more than a 30 V difference in P0.X+ and P0.X–
terminals. Exceeding 30 V differential voltage could cause damage to the
photocouplers.
(NI 6521 Only)
The 30 V differential voltage can have up to ±120 V
common-mode voltage compared to chassis/digital ground of the NI 6521
device.
Description
Isolated input ports, positive terminals—Each of
these terminals serves as the signal input. You can
connect either end of the input signal to it, regardless
of whether the level is positive or negative.
Isolated input ports, negative terminals—Each of
these terminals serves as the signal input. You can
connect either end of the input signal to it, regardless
of whether the level is positive or negative.
13
NI 6520/6521 User Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ni 6521

Table of Contents