Gas Piping

Burner Piping
The burner is factory assembled and shipped as ordered.
NOTE: If it is necessary to redirect piping, remove the
outer four bolts only
replace bolts. When reassembling, be sure that:
• ratio regulator spring column
• the bypass regulator spring column is pointing up
• arrow on the ratio regulator points in the direction of
gas flow
• integral fuel orifice and o-rings
• the same straight run of pipe
the ratio regulator and the burner.
Do not attempt to redirect piping by removing the
inner circle bolts
damaged.
Figure 3.6 Burner Piping
Eclipse Winnox Burner, WX Series, V2, Installation Guide 111, 2/26/2010
. Rotate the rear cover and
is pointing up
are reinstalled
remains between
CAUTION
. Internal burner parts will be
Do not alter the bypass regulator. The NFPA
requires
that
the
appropriately vented and protected.
For applications in which the Winnox is
operating indoors, a vent limiting device is
installed in the bypass regulator.
For applications in which the Winnox is
operating outdoors, an insect/rain protector is
installed in the bypass regulator.
Supply Piping
Inlet pressure to the ratio regulator must stay within
specified limits. Refer to the appropriate Winnox
datasheet, series 111.
• Locate the valve train close to the burner. The gas
must reach the burner during the fixed trial for
ignition period.
• Sufficiently size the shut off valve in the valve train.
• Make sure piping is large enough to accommodate
flow required to meet burner input.
• Minimize piping elbows.
• Install fuel flow measurement device
from the burner inlet.
• If necessary to maintain inlet pressures to the
burner (see datasheet for your burner), install a gas
pressure regulator
and downstream of the valve train and fuel
measurement device
Tap E
Figure 3.7 Supply Piping
Pipe Connections
Installation of a pipe union in the gas line is recommended
to simplify burner removal.
Use of flexible pipe is optional.
NOTE: Flexible pipe causes higher pressure drops than
standard pipe. Consider this when sizing your gas lines.
CAUTION
bypass
regulator
upstream
upstream of the burner inlet
.
Main gas
shut-off
valve train
be
9

Advertisement