Cod. 6328424 - 04/2017 MURELLE HE 70 R ErP USER, INSTALLATION AND SERVICING INSTRUCTIONS ENSURE THAT THESE INSTRUCTIONS ARE LEFT FOR THE USER AFTER COMPLETION OF THE BENCHMARK SECTION PLEASE READ THE IMPORTANT NOTICE WITHIN THIS GUIDE REGARDING YOUR BOILER WARRANTY 199838...
For the first year all of our appliances are protected by our manufacturer’s guarantee which covers both parts and labour. As you would expect from Sime Ltd, it is our aim to provide our valued customers with the best in after sales and service.
VENTILATE THE AREA BY OPENING DOORS AND WINDOWS contact the gas emergency service on 0800111999. Murelle HE 70 R ErP: Gas Council number 47-283-84 CONFORMITY Our Company declares that MURELLE HE 70 R ErP boilers comply with the essential requirements of the following directives: - Boiler Efficiency Directive 92/42/EEC...
(from 20% to 100% of power) desig- pendent from each other. For optimum MURELLE HE 70 R ErP are premixed gas ned for single installation and in modular installation and operation, always follow condensing heating modules for heating systems with several generators con- the instructions provided in this manual.
Page 7
TECHNICAL FEATURES MURELLE HE 70 R ErP Heat output Nominal (80-60°C) (Pn max) 63.4 Nominal (50-30°C) (Pn max) 69.4 Reduced (80-60°C) (Pn min) 13.6 Reduced (50-30°C) (Pn min) 15.3 Heat input (*) Nominal (Qn max - Qnw max) 65.0 Reduced (Qn min - Qnw min) 14.0...
Page 8
FUNCTIONAL DIAGRAM (fig. 2) Gas valve Condensate drain trap Heating flow sensor (SM) Safety thermostat 100°C Exhaust sensor (SF) Primary heat exchanger Heating return sensor (SR) Water pressure transducer Auto air vent Pump high efficiency Drain vent Safety valve 3.5 bar CONNECTIONS Heating return Heating flow...
Page 9
TECHNICAL DATA PLATE (fig. 3/a) MODEL TYPE SERIAL NUMBER CODE YEAR OF CONSTRUCTION PIN NUMBER DIRECTIVE OF REFERENCE WATER CONTENT IN BOILER HEAT INPUT MAX HEAT INPUT MIN HEAT OUTPUT MAX (80-60°C) HEAT OUTPUT MIN (80-60°C) HEAT OUTPUT MAX (50-30°C) HEAT OUTPUT MIN (50-30°C) MAX OPERATING PRESSURE MAX OPERATING PRESSURE...
Take ceiling) care that the position of low level vents MURELLE HE 70 R ErP can be installed would not subject to adverse weather When installed as a class B appliance in boiler rooms whose size and require- conditions, ie flooding.
Page 11
Installed in a room in MODBUS. High level (within 15% of the room height The board is placed on the back of the Then press again, simultaneously, the from ceiling) - 2cm²/KW of net heat control panel. and the buttons for 2 seconds until input Low level (low as possible within 1 metre Access the board and chose the desired...
Page 13
(PAR 17 INST) according to Table PAR The RS-485 board can be used for 17 INST. MODBUS communication every board and the PAR 16 as indicated in MURELLE HE 70 R ErP boiler. the figure. COMUNICAZIONE MODBUS DIP SWITCH CONNETTORE MODBUS COMMUNICATION CABLATO CN10 (cod.
Page 14
MODBUS BOILER VARIABLES LIST Function Variable description Digital variables Boiler CH Enable/Request D R/W Request CH zone 1 Enable DHW preparation Boiler DHW Enable D R/W Boiler Water Filling Function D R/W Not used State CH zone 1 Boiler CH Mode State preparation DHW Boiler DHW Mode Boiler Flame Status...
Page 15
CASCADE+MODBUS mode (fig. 4/d) CONNETTORE CABLATO This mode allows for MODBUS commu- (cod. 6319173) nication of at least two boilers in cascade WIRED CONNECTOR and is performed by requesting another (cod 6319173) RS-485 board provided in the kit code 8092244. ATTENTION: Communication will occur only with the MASTER boiler, (boiler with PAR 15 = 0), interpreting the casca-...
Page 16
3 m. termination important to clean the system using suitable products. Sime recommend the should be into an external gully or purpose 2.3.2 Filter on the gas pipe use of FERNOX products for the flushing made soakaway.
Page 17
2.4.3 Requirements for sealed water When the boiler works at low temperatu- 2.5.4 Maximum usable systems MURELLE HE 70 R ErP re is possible to use normal chimneys at length for coaxial (fig. 5/b) the following conditions: ø 80/125 flues –...
Page 18
Type B 80 mm accessories Code Description Load loss mm H 2 0 8077450A single) 90° bend 8077450 (6 pieces) 8077351A (single) 1000mm Extension 8077351 (6 pieces) 8077350A (single) 500mm Extension 8077350 (6 pieces) 8091300 Articulated Tile 8091212B Roof terminal (1381mm) 6296513 Extension with test point (250mm)
Page 19
Type C (separate ø 80 flues and Type C (separate ø 80 flues) coaxial exhaust terminal) 80 mm accessories WARNING: Code Description Load loss mm - Installations with roof exit terminal (4a) and coaxial exhaust (13) require the Inlet Exaust use of a condensation recovery (12) that 8077450A (single) 90°...
Page 20
The electric power supply to the boiler Pmin must be 230V - 50Hz single-phase throu- to a remote control unit SIME HOME, gh a 3 A fused main switch, with at least supplied on request (code 8092280/81). 12. Visualizzazione codice errore...
Page 21
TABLE 2 Terminal position Minimum spacing Directly below an openable window, air vent or any other ventilation opening 300 mm 12 in Below guttering, drain pipes or soil pipes 75 mm 3 in C/D Below eaves, balconies or carport roof (*) 200 mm 8 in From vertical drain pipes or soil pipes...
Page 22
Fuse (4 AT) Zone 2 environment thermostat Ignition transformer D.H.W. sensor L. 2000 (optional) code 6319162 Pump high efficiency Remote control code 6319160 SIME HOME (optional) code 6319164 Ignition electrode External sensor (optional) code 6316203 Ionisation electrode Programming clock (optional) code 6316202...
ON = Electricity supply to boiler is on PC CONNECTION OFF = Electricity supply to boiler is on but not ready To be used only with the SIME programming kit and only for functioning. However, the protection fun- by authorised personnel. Do not connect other electronic ctions are active.
Page 24
ACCESS TO INSTALLER’S INFORMATION For access to information for the installer, press the key (3 fig. 14). Each time the key is pressed, the display moves to the next item of information. If expansion boards (MIXED ZONE o INSOL) are connected, the related info will be displayed. If the key is not pressed, the system automatically quits the function.
Page 25
18. Display of heating return temperature sensor (SR) 29. Display of valve operation with board MIXED ZONE 2 (respectively ON and OFF) 18. Visualizzazione valore sonda ritorno riscaldamento (SR) 29. Visualizzazione comando chiusura valvola con schedino ZONA MIX 2 (rispettivamente ON e OFF) 19.
Page 26
1 = Enabled after 60 seconds, or by pressing one of the Allocation of SIME HOME channels 0 = Not assigned control keys (2 fig. 12). 1 = Circuit 1 e in h x 100 (es. 14.000 e 10)
Page 27
BOILER PAR 2 PARAMETERS INSTALLER Instantanious with diverter valve and flowmeter EXPANSION CARD Instantanious with diverter valve, PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT flowmeter and solar system MEASUREMENT UNIT SETTING Number of expansion boards 0 ... 3 Remote control cylinder with Mix valve stroke time 0 ...
Page 28
Fig. 13 the system. – Interface with the following electro- nic systems: remote control SIME ting return sensor (SR) or the exhaust 3.7.1 Functioning cycle HOME code 8092280/81, thermal...
Page 29
to light. if after the third attempt the When voltage returns, the boiler will shown as a function of rate of flow in the flame has not been recognised, the automatically start up again. graph in fig. 14. boiler will lockout ALL06. This may If fitted, the speed of the modulating be due to worn or distorted ionisa- pump system is set as default (installa-...
Page 30
MURELLE 50 HE R - UK “MURELLE HE 70 R ErP” WITH KIT COMPENSATOR CODE 8101586 AND DHW CYLINDER (fig. 15) 1 Gas valve 2 Condensation drain trap 3 DHW Cylinder pump (not supplied) 4 Fan 5 Heating flow sensor (SM) 6 Safety thermostat 100°C...
Page 31
(fig. 15/a). stion circuit and working gas supply Procedure for checking the combu- pressure. If required contact Sime Set up the boiler(s) to operate at maximum rate as described in 4.5.1 stion. Ltd for further assistance.
Page 32
The boiler is supplied as standard with the SIT 848 SIGMA gas valve (fig. 16). ne codice errore GAS CONVERSION This operation must be performed by authorised personnel using original Sime components. ne codice errore omalia Inlet pressure intake 4.2.1 New fuel configuration...
Page 33
ATTENTION Codice/Code 8104981 Modello/Model MURELLE HE 70 R ErP Before removing or refitting Matricola/Serial n. 9999999999 the front panel of the boiler, open the small upper plastic PAR 1 = 58 (G20) / 59 (G31) door. PAR 2 = 5 Fig.
Page 34
by means of the installer parameter PAR 43: 0 = Not activated function 1 = Curve setting A 2 = Curve setting B 3 = Curve setting A + B The turning off of the function happens clicking on the button OFF (return of PAR 43 to the value 0) or automatically at the end of the function.
Page 35
FUNCTIONING ERRORS Apre Circuito When there is a functioning error, an Circuito riscaldamento 2 alarm appears on the display and the riscaldamento 2 blue luminous bar may becomes red. Descriptions of the errors with relative alarms and solutions are given below: Circuito riscaldamento 2 –...
Page 36
Apre – SAFETY/LIMIT THERMOSTAT ERROR ALARM 07 (fig. 23/f) If the connection with the safety ther- Circuito mostat/limit thermostat is interrupted, riscaldamento 2 the boiler will stop; the flame control will remain waiting to be switched off for one minute, keeping the system pump on for that period.
Page 37
zone) Circuito Circuito riscaldamento 2 – FAN ERROR “ALL 15” (fig. 23/m) – SAFETY THERMOSTAT INTERVEN- – AUXILIARY SENSOR ERROR (S3) “ALL riscaldamento 2 The fan speed does not fall within the TION SECOND MIXED ZONE “ALL 22” 26” (fig. 23/20) rated speed range.
Page 38
TION ERROR “ALL 32” (fig. 23/w) scade connection, error codes 70 and 71 When the boards connected to the RS-485 will appear on the SIME HOME remote control display: are not enough and/or at least one of them it is not mixing zone board, the boiler stops - ALARM 70 and anomaly ALL 32 is displayed.
GAS BOILER SYSTEM COMMISSIONING CHECKLIST This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference. Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty.
SERVICE RECORD It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed. Service Provider Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions. SERVICE 01 SERVICE 02 Date:...
FAULT FINDING If an electrical fault occurs on the appli- SHORT CIRCUIT CHECK approx.: 240 V ac. ance the preliminary electrical system – Test leads from L to E “ ” meter checks must be carried out first. Switches turned FULL ON - meter set on reads approx.
SAFETY STAT should spares or replacement parts be used RHS panel. that are not supplied by Sime Ltd and only suit- Isolate the flow and return valves, and drain the Isolate the electrical and gas supply. able qualified personnel are permitted to work boiler using the drain vents provided.
Page 47
8104981 MURELLE HE 70 R ErP Position Code Description 6138533 Right hand side frame part 6138632 Left hand side frame part 6255431 Expansion vessel lower support 6256750 Transformer fixing bracket 6138900 Frame assembly lower side 6266081 Rear panel 6256751 Upper protection fixing bracket 6267156 Main exchanger support.
Page 48
6243837 Gas valve 6277461 Pipe connecting gas valve-mixer 6280590 Three way fitting + cap kit 6098315 Ignition transformer 6010872 Upper protection shield 6083062 Flue inlet flange Ø 80 6248802 Gasket Ø 80 6190001 Intake terminal Ø 80 6001171 Air intake pipe 60 2051200 Hose clamp Ø...
APPENDIX 1 INDUSTRY GUIDANCE FOR INSTALLERS ON CONDENSATE DRAINAGE PIPE INSTALLATION This guidance is endorsed by HHIC members. 1. BACKGROUND During recent winters the UK has experienced prolonged spells of extremely cold weather - down to minus 20 C and below in many areas. This resulted in a significant increase in the number of calls to boiler manufacturers and heating engineers from householders with condensing (high efficiency) boilers where the condensate drainage pipe had frozen and become blocked with ice, causing the boiler to shut down.
Page 50
2.1 INTERNAL TERMINATION: Wherever possible, the condensate drainage pipe should be terminated at a suitable internal foul water discharge point such as (a) an internal soil and vent stack or (b) an internal kitchen or bathroom waste pipe, washing machine waste pipe etc. A suitable permanent connection to the foul waste pipe should be used.
Page 51
The use of fittings, elbows etc should be kept to a minimum and any internal “burrs” on cut pipework should be removed so that the internal pipe section is as smooth as possible. The customer/householder should be advised that even with the above measures this type of installation could freeze, and that if this were to occur then boiler shutdown could result, requiring remedial action - possibly involving a chargeable engineer call-out.
Page 52
NOTES The Benchmark Commissioning Checklist should be completed as required to record details of the condensate drainage pipe installation. Where an external condensate drainage pipe is installed, the customer should be made aware of the risks and consequences of its freezing and offered the option to fit trace heating (or other measures approved by the boiler manufacturer or service organisation).
Page 53
Figure 1 – Connection of condensate drainage pipe to internal soil and vent stack Boiler Visible air break 75 mm trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler Soil and vent stack Invert 450 mm minimum up to three storeys...
Page 54
Figure 2(a) – Connection of a condensate drainage pipe downstream of a sink, basin, bath or shower waste trap Boiler Visible air break 75 mm trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler.
Page 55
Figure 2(b) – Connection of a condensate drainage pipe upstream of a sink, basin, bath or shower waste trap Boiler Visible air break at plug-hole 75 mm sink, basin, bath or shower waste trap Sink, basin, bath or shower with integral overflow Open end of condensate drainage pipe direct into gully 25 mm min below grating but above water level;...
Page 56
Figure 3 – Connection of a condensate pump - typical method (NB manufacturer’s detailed instructions should be followed). IND GUIDE INST 10-11 HHIC REF T11/0027BRev8...
Page 57
Figure 4 – Connection of condensate drainage pipe to external soil and vent stack Boiler 450 mm minimum up to three storeys Visible air break Minimum internal diameter 19 mm 75 mm trap Pipe size transition point Visible air break and trap not required if Minimum internal diameter 30 mm there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler.
Page 58
Figure 6 – External drain, gully or rainwater hopper Boiler Visible air break 38 mm minimum trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 38 mm incorporated into the boiler External length of pipe 3 m maximum Open end of condensate drainage pipe direct into gully 25 mm min below grating but above water level;...
Page 59
Figure 6 – External drain, gully or rainwater hopper Boiler Visible air break 38 mm minimum trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 38 mm incorporated into the boiler External length of pipe 3 m maximum Open end of condensate drainage pipe direct into gully 25 mm min below grating but above water level;...
Page 60
Figure 7 – Example of a purpose-made soakaway Condensate discharge pipe from boiler Ground (this section of the condensate drainage pipe may be run either above or below ground level); End cut at 45 ° Diameter 100 mm minimum plastic tube Bottom of tube sealed Limestone chippings Two rows of three 12 mm holes at 25 mm centres, 50 mm from bottom of tube and...
Apre USER INSTRUCTIONS Apre BOILER IGNITION (fig. 24) The first ignition of the boiler must be carried out by qualified technical per- sonnel. Successively, if it is necessary to start up the boiler again, adhere strictly to the following instructions: open the Circuito gas isolation valve to allow the flow of the riscaldamento 2...
Page 62
From ALL 20 to ALL 35 Request assistance from qualified Fig. 27/c technical personnel. – ALL 70 and ALL 71 – ALL 07 (fig. 27/d) These alarms appear on the SIME Press the key of the controls (2) HOME remote control display. Re-...
PRODUCT DETAILS Murelle HE 70 R ErP Classe efficienza energetica stagionale riscaldamento Clase de eficiencia energética estacional en calefacción Classe de eficiência energética do aquecimento ambiente sazonal C.H. energy efficiency class Potenza termica (kW) Potencia térmica (kW) Potência calorífica (kW) Heat output (kW) Consumo annuo di energia riscaldamento (GJ) Consumo anual de energía en calefacción (GJ)