The Benchmark Scheme Sime Ltd is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimi- se safety, efficiency and performance.
Page 13
COMUNICAZIONE MODBUS DIP SWITCH CONNETTORE MODBUS COMMUNICATION CABLATO CN10 (cod. 6319165) WIRED CONNECTOR CN10 (code 6319165) – INSTALLER PARAMETERS SETTING: – SCHEDINO RS-485 RS-485 BOARD PAR 16 MODBUS MODE -- = Disabled 1...31 = Slave from 1 to 31 (ATTENTION: Each slave must be assigned with a different number).
Page 14
MODBUS BOILER VARIABLES LIST Function Variable description Digital variables Request CH zone 1 Boiler CH Enable/Request D R/W Enable DHW preparation Boiler DHW Enable D R/W Not used Boiler Water Filling Function D R/W State CH zone 1 Boiler CH Mode Boiler DHW Mode State preparation DHW Boiler Flame Status...
Page 15
CONNETTORE CABLATO (cod. 6319173) WIRED CONNECTOR (cod 6319173) COMUNICAZIONE MODBUS MODBUS COMMUNICATION DIP SWITCH GESTIONE IN MODBUS MODBUS MANAGEMENT 1 2 3 Module with 1 RS-485 board Module with 2 RS-485 board Cavo kit INSOL/ZONA MIX INSOL / Kit INSOL/MIX ZONE cable Schedino board and kit board INSOL/ZONA MIX e kit...
Page 21
BASIC SYSTEM SYSTEM WITH A DIRECT ZONE AND ROOM THERMOSTAT, OR WITH A CLIMATIC REGULATOR CR 53 (Code 8092227) OR WITH REMOTE CONTROL CR 73 (Code 8092226) AND EXTERNAL SENSOR (Code 8094101) PARAMETERS SETTINGS If using CR 53 set parameter 10 to 2 (PAR 10 = 2)
BASIC SYSTEM MULTI-ZONE SYSTEM WITH PUMP, ROOM THERMOSTAT AND EXTERNAL SENSOR (Code 8094101) BASIC SYSTEM MULTI-ZONE SYSTEM WITH PUMP, ROOM THERMOSTAT AND EXTERNAL SENSOR (Code 8094101) BASIC SYSTEM MULTI-ZONE SYSTEM WITH VALVE, ROOM THERMOSTAT, REMOTE CONTROL CR 73 (Code 8092226) AND EXTERNAL SENSOR (Code 8094101) PARAMETERS SETTINGS To use the remote control...
Page 23
BASIC SYSTEM MULTI-ZONE SYSTEM WITH VALVE, ROOM THERMOSTAT, REMOTE CONTROL CR 73 (Code 8092226) AND EXTERNAL SENSOR (Code 8094101) PARAMETER SETTING To use the remote control (CR) as room reference for a zone, set: PAR 7 = 1 Set the opening time of the zone valve VZ: PAR 33 = “OPENING TIME”...
Page 24
SYSTEM WITH DOUBLE TEMPERATURE OUTPUT MULTI-ZONE SYSTEM WITH PUMP, CHRONOTHERMOSTAT AND EXTERNAL SENSOR (Code 8094101) ZONA ZONA NIGHT GIORNO NOTTE ZONE ZONE (70ϒ C) (50ϒ C) (70°C) (50°C) SYSTEM WITH REMOTE CYLINDER UNIT AFTER THE HYDRAULIC SEPARATOR BOLLITORE D.H.W. TANK...
Page 25
SYSTEM WITH MIXER VALVE SYSTEM WITH ONE DIRECT ZONE, ONE MIXED ZONE, ONE KIT MIXED ZONE (Code 8092234), REMOTE CONTROL CR 73 (Code 8092226) AND EXTERNAL SENSOR (Code 8094101) PARAMETERS SETTINGS To use the remote control (CR) as remote control panel for the boiler rather than as room reference, set: PAR 7 = 0...
Page 26
SYSTEM WITH MIXER VALVE SYSTEM WITH TWO MIXED ZONE INDEPENDENT, TWO KITS MIXED ZONE (Code 8092234) AND EXTERNAL SENSOR (Code 8094101) SYSTEM SOLAR SYSTEM WITH TWO MIXED ZONE INDEPENDENT, ONE DIRECT ZONE, TWO KITS MIXED ZONE (Code 8092234), ONE KIT SOLAR INSOL (Code 8092235), REMOTE CONTROL CR 73 (Code. 8092226) AND EXTERNAL SENSOR (Code 8094101) Murelle HM T / HE R (M) (CR)
Page 29
1. Display of external temperature, only when 9. Display fan speed in rpm x 100 (e.g. 4.800 and 1850 rpm) 1. Visualizzazione temperatura esterna 9. Visualizzazione numero giri ventilatore in rpm x 100 (es. 4.800 e 1.850 rpm) external sensor connected solo con sonda esterna collegata 2.
Page 30
18. Display of heating return temperature sensor (SR) 29. Display of valve operation with board MIXED ZONE 2 (respectively ON and OFF) 18. Visualizzazione valore sonda ritorno riscaldamento (SR) 29. Visualizzazione comando chiusura valvola con schedino ZONA MIX 2 (rispettivamente ON e OFF) 19.
Page 31
PARAMETERS INSTALLER FAST CONFIGURATION PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT MEASUREMENT UNIT SETTING Combustion configuration -- = ND “- -” 1 ... 31 Hydraulic configuration -- = ND “- -” 1 ... 14 Timetable 2 programmer 1 = DHW + Recirc. pump 2 = DHW 3 = Recirculation pump Pressure transducer disabler...
Page 32
BOILER PAR 2 PARAMETERS INSTALLER Instantanious with diverter valve and flowmeter EXPANSION CARD Instantanious with diverter valve, PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT flowmeter and solar system MEASUREMENT UNIT SETTING Number of expansion boards 0 ... 3 Remote control cylinder with Mix valve stroke time 0 ...
Page 33
ATTENTION: curves are calculated at an ambient temperature of 20°C. The user can act on the boiler controls to change the envi- ronment set for which the bend has been calculated by ±5°C. Fig. 13 TABLE 4 (SM - SR - SF sensors)
Page 34
con by-pass By-pass inserted senza by-pass By-pass excluded POMPA FISSA FIXED PUMP POMPA MODULANTE MODULATING PUMP WILO-YONOS PARA PWM (M) WILO-YONOS PARA PWM (M) 1000 1200 PORTATA (l/h) FLOW RATE (l/h) Fig. 14 REFERENCE BY-PASS POSITION RIFERIMENTO POSIZIONE BY-PASS Fig. 14/a...
Page 36
Fig. 17 Fig. 16 MAX power (Methane) (Propane) 9,3 ±0,2 10,2 ±0,3 MODES PAR 1 METHANE Single (35 R) (G 20) Sequence/cascade MIN power (Methane) (Propane) 8,4 ±0,2 10,0 ±0,3 PROPANE Single (35 R) (G 31) Sequence/cascade...
Page 37
Codice/Code 8111200 Modello/Model MURELLE HE 35 R (M) Matricola/Serial n. 9999999999 PAR 1 = 3 (G20) / 11 (G31) PAR 2 = 5 Fig. 19 Fig. 20...
Page 38
Fig. 21 [TVw] Fig. 22 [Tag A + B Flow temperature setpoint Period in days Start day Functional heating Floor curing heating Fig. 22/a...
Page 39
4.5.4 WILO-YONOS PARA PWM pump diagnose and remedy (fig. 22/b) LED diagnose and remedy Led color Meaning Diagnostic Cause Remedy Continuous green Normal running Pump run as expec- Normal operation ted or is faced to a phenomenon that shortly affects its running Red/green blinking Abnormal situation...
GAS BOILER SYSTEM COMMISSIONING CHECKLIST This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference. Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty.
SERVICE RECORD It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed. Service Provider Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions. SERVICE 01 SERVICE 02 Date:...
Page 49
MURELLE HE 35 R - MURELLE HE 35 R M Posiz. Codice Descrizione 6138533 Right hand side frame part 6138632 Left hand side frame part 6255431 Expansion vessel lower support 6138894 Frame assembly lower side 6266081 Rear panel...
Page 50
6302000 Plastic pin 6319650 Bitron transducer cap 6304430 casing left/right side panel 6304231 Casing front panel 6272312 Circulating pump MURELLE HE 35 R 6040211 Pressure relief valve 3 bar 6319603 Discharger cock 6120533 C.H Nipple 6273608 Water pressure transducer 6319641...
Page 51
6305010 connection cover 6305020 Time programmer cover 6301465 PCB expansion 6272320 Modulating circulating pump MURELLE HE 35 R M 5198890 Technyl hydraulic group 6319699 Split pin kit for hydraulic gro 6319698 O-ring kit for hydraulic group 6211792 Hydraul. group Bitron caps kit...
Page 52
INDUSTRY GUIDANCE FOR INSTALLERS ON CONDENSATE DRAINAGE PIPE INSTALLATION This guidance is endorsed by HHIC members. 1. BACKGROUND During recent winters the UK has experienced prolonged spells of extremely cold weather - down to minus 20 C and below in many areas. This resulted in a significant increase in the number of calls to boiler manufacturers and heating engineers from householders with condensing (high efficiency) boilers where the condensate drainage pipe had frozen and become blocked with ice, causing the boiler to shut down.
2.1 INTERNAL TERMINATION: Wherever possible, the condensate drainage pipe should be terminated at a suitable internal foul water discharge point such as (a) an internal soil and vent stack or (b) an internal kitchen or bathroom waste pipe, washing machine waste pipe etc. A suitable permanent connection to the foul waste pipe should be used.
Page 54
The use of fittings, elbows etc should be kept to a minimum and any internal “burrs” on cut pipework should be removed so that the internal pipe section is as smooth as possible. The customer/householder should be advised that even with the above measures this type of installation could freeze, and that if this were to occur then boiler shutdown could result, requiring remedial action - possibly involving a chargeable engineer call-out.
Page 55
NOTES The Benchmark Commissioning Checklist (located at the back of the boiler installation manual) should be completed as required to record details of the condensate drainage pipe installation. Where an external condensate drainage pipe is installed, the customer should be made aware of the risks and consequences of its freezing and offered the option to fit trace heating (or other measures approved by the boiler manufacturer or service organisation).
Page 56
Figure 1 – Connection of condensate drainage pipe to internal soil and vent stack Boiler Visible air break 75 mm trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler Soil and vent stack Invert 450 mm minimum up to three storeys...
Page 57
Figure 2(a) – Connection of a condensate drainage pipe downstream of a sink, basin, bath or shower waste trap Boiler Visible air break 75 mm trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler.
Page 58
Figure 2(b) – Connection of a condensate drainage pipe upstream of a sink, basin, bath or shower waste trap Boiler Visible air break at plug-hole 75 mm sink, basin, bath or shower waste trap Sink, basin, bath or shower with integral overflow Open end of condensate drainage pipe direct into gully 25 mm min below grating but above water level;...
Page 59
Figure 3 – Connection of a condensate pump - typical method (NB manufacturer’s detailed instructions should be followed). IND GUIDE INST 10-11 HHIC REF T11/0027BRev8...
Page 60
Figure 4 – Connection of condensate drainage pipe to external soil and vent stack Boiler 450 mm minimum up to three storeys Visible air break Minimum internal diameter 19 mm 75 mm trap Pipe size transition point Visible air break and trap not required if Minimum internal diameter 30 mm there is a trap with a minimum condensate seal of 75 mm incorporated into the boiler.
Page 61
Figure 5 – External termination to rainwater downpipe (NB only combined foul/rainwater drain) Condensate discharge pipe from boiler Air gap Pipe size transition point 68 mm PVCu strap-on fitting Water/weather proof insulation Minimum internal diameter 19 mm 43 mm 90° male/female bend Minimum internal diameter 30 mm External rain water pipe into foul water End cut at 45 °...
Page 62
Figure 6 – External drain, gully or rainwater hopper Boiler Visible air break 38 mm minimum trap Visible air break and trap not required if there is a trap with a minimum condensate seal of 38 mm incorporated into the boiler External length of pipe 3 m maximum Open end of condensate drainage pipe direct into gully 25 mm min below grating but above water level;...
Page 63
Figure 7 – Example of a purpose-made soakaway Condensate discharge pipe from boiler Ground (this section of the condensate drainage pipe may be run either above or below ground level); End cut at 45 ° Diameter 100 mm minimum plastic tube Bottom of tube sealed Limestone chippings Two rows of three 12 mm holes at 25 mm centres, 50 mm from bottom of tube and...