General Inspection; Measuring The Insulation Resistance During The Course Of Maintenance Work - Siemens SIMOTICS HT Series Operating Instructions & Installation Instructions

Low-voltage motor
Table of Contents

Advertisement

Maintenance
9.1 Inspection and maintenance
9.1.4

General inspection

● Check that the installation conditions are observed. Perform the following checks after
● If you detect any deviations during the inspection, you must rectify them immediately. They
9.1.5

Measuring the insulation resistance during the course of maintenance work

Measuring the insulation resistance and polarization index (PI) provides information on the
condition of the machine. It is therefore important to check the insulation resistance and the
polarization index at the following times:
● Before starting up a machine for the first time
● After an extended period in storage or downtime
● Within the scope of maintenance work
The following information is provided regarding the state of the winding insulation:
● Is the winding head insulation conductively contaminated?
● Has the winding insulation absorbed moisture?
As such, you can determine whether the machine needs commissioning or any necessary
measures such as cleaning and/or drying the winding:
● Can the machine be put into operation?
● Must the windings be cleaned or dried?
Detailed information on testing and the limit values can be found here:
100
approx. 16 000 operating hours or at the latest after two years:
Checking
The electrical parameters are maintained
The permissible bearing temperatures are not exceeded (Page 85)
The smooth running characteristics and machine running noise have not
deteriorated
The foundation has no cracks or indentations. (*)
The machine is aligned within the permissible tolerance ranges.
All the fixing bolts/screws for the mechanical and electrical connections
have been securely tightened
All the potential connections, grounding connections and shield supports
are correctly seated and properly bonded
The winding insulation resistances are sufficiently high (Page 47)
Any bearing insulation is fitted as shown on the plates and labels
The CABLES and insulating parts and components are in good condition
and there is no evidence of discoloring
Condensation can freely flow away.
(*) This check can be made at standstill or when running.
may otherwise cause damage to the machine.
When the
motor is
running
X
X
X
X
SIMOTICS HT Series HT-direct 1FW4...1......A
Operating Instructions 11/2018
At stand‐
still
X
X
X
X
X
X
X
X