GEM 539 eSyDrive Operating Instructions Manual page 14

Motorized globe valve
Hide thumbs Also See for 539 eSyDrive:
Table of Contents

Advertisement

5 Technical data
5.6 Electrical data
Supply voltage:
5.6.1 Analogue input signals
5.6.1.1 Set value
Input signals:
Input type:
Input resistance:
Accuracy/linearity:
Temperature drift:
Resolution:
Reverse battery
protection:
Overload proof:
5.6.1.2 Process actual value
Input signals:
Input type:
Input resistance:
Accuracy/linearity:
Temperature drift:
Resolution:
Reverse battery
protection:
Overload proof:
GEMÜ 539
Voltage
Rating
Operating mode
(OPEN/CLOSE
operation)
Operating mode
(control operation)
Reverse battery
protection
0/4 - 20 mA; 0 – 10 V DC (selectable using software)
passive
250 Ω
≤ ±0.3% of full flow
≤ ±0.1% / 10°K
12 bit
No
Yes (up to ± 24 V DC)
0/4 - 20 mA; 0 – 10 V DC (selectable using software)
passive
250 Ω
≤ ±0.3% of full flow
≤ ±0.1% / 10°K
12 bit
No
Yes (up to ± 24 V DC)
Actuator size 0
Actuator size 1
Uv = 24 V DC ± 10%
Max. 28 W
Continuous duty
Class C acc. to EN 15714-2
14 / 34
Actuator size 2
Max. 65 W
Max. 120 W
Yes
www.gemu-group.com

Advertisement

Table of Contents
loading

Table of Contents