Power Supply X2; Alarm Relay Terminals X7; Fibre Optic (Fo) Connections R And T; Pluging The D-Sub Connector - Siemens 7XV5450 0BA00 Operating Instructions Manual

Optical mini-starcoupler
Table of Contents

Advertisement

4.2.1

Power supply X2

The wires for the auxilliary voltage are screwed on terminal X2 at he bottom side of
the device. The assignment of the terminals is printed at the front side or can be read
in this manual. Because the device has no ON/OFF switch this switch must be
installed external if it´s necessary.
Connection to screw terminals:
Stripping length:
Cable cross section:
(Single core cable or litz wire)
4.2.2

Alarm relay terminals X7

X7 offers a potential free contact, which is closed if the device fails. The loss of the
power supply is a device failure.
The wires for the alarm contacts are screwed on terminal X7 at he bottom side of the
device. The assignment of the terminals is printed at the front side or can be read in
this manual.
Connection to screw terminals:
Alarm relay terminals:
Stripping length:
4.3

Fibre Optic (FO) connections R and T

Only optical fibres prepared according the regulations are to be used. The
admissible optical budget is to be observed
FO-types (only multimode) and max. distance see technical datas.
Transmitter diodes are printed with T1 to T5.
Receiver diodes are printed with R1 to R5.
The FO-cables must be crossed, that means a FO-connection is done between
Transmitter and Receiver and vice versa.
4.4

Pluging the D-Sub connector

After having plugged the D-Sub connector, make sure it is screwed tightly.
Page 24 of 28
Note
When installing optical fibres the prescripted bending
radius is to be observed.
Mini-Star coupler
C53000-B1140-C595-1
3 mm to 5 mm
2
2
1.5 mm
to 2.5 mm
2
max. 2.5 mm
3 mm to 5 mm
7XV5450-0BA00