15.1 Auxiliary Alarm Switch

The control is equipped with two Auxiliary Alarm termi-
nals, labeled TB4 and TB5 which are typically utilized in
series with a condensate switch but could also be used
with compatible CO
2
The auxiliary alarm switch must be normally closed and
open when the alarm occurs. For example, a normally
closed condensate switch will open when the base pan's
water level reaches a particular level. The control will
respond by turning off the blower motor and outdoor unit
and displaying the proper fault codes. If the switch is
later detected closed for 30 seconds, normal operation
resumes and the error message is removed. (The switch
is closed as part of the default factory setting.) The error
will be maintained in the equipment's fault history. See
Figures 15 and 16 for the connection location.