Download Print this page

Huawei UPS5000-E Series Quick Manual page 9

40-320 kva power modules
Hide thumbs Also See for UPS5000-E Series:

Advertisement

4. Connect the mains input cables to mains
input power distribution terminals 1L1, 1L2,
and 1L3, respectively.
Connect the bypass input cables to bypass
input power distribution terminals 2L1, 2L2,
and 2L3, respectively.
Connect the N wires of the mains and
bypass input cables to the input power
distribution terminal N.
M12x13.5 (8 PCS)
46 N•m
6. Connect battery cables to battery positive
and negative terminals and neutral wires on
the UPS cabinet.
M12x13.5 (3 PCS)
46 N•m
8. Install the panel removed from the UPS cabinet on the exterior of the top entry cabinet.
5. Connect AC output power cables to the
output terminals N, U, V, and W on the
UPS cabinet.
M12x13.5 (4 PCS)
46 N•m
7. Connect signal cables to the UPS through the
cable trough in the top entry cabinet.
Install the cable trough near the front of the
UPS cabinet. If the cable trough is near the
rear of the UPS cabinet, remove it and install
it near the front of the UPS cabinet.
8