Connecting Cables to the UPS5000-E-320K-F320T
Take the cable tray covers for the power
cables and signal cables out of the cabinet,
drill holes on the cable tray cover for the power
cables, attach grommet strips on the hole
edges for protecting cables, and reinstall the
cable tray cover for the power cables.
1. Remove the cover from the power
distribution subrack.
2. Remove the copper bars between mains
input terminals and bypass input terminals.
3. Connect the ground cable to the UPS.
In the preceding figure, circled wiring terminals
are primary ones and must connect to the
ground cable.
9
M12x13.5 (4 PCS)
46 N•m