Download Print this page

Huawei UPS5000-E Series Quick Manual page 11

40-320 kva power modules
Hide thumbs Also See for UPS5000-E Series:

Advertisement

4. Connect the mains input cables to mains
input power distribution terminals 1L1, 1L2,
and 1L3, respectively.
Connect the bypass input cables to bypass
input power distribution terminals 2L1, 2L2,
and 2L3, respectively.
Connect the N wires of the mains and
bypass input cables to the input power
distribution terminal N.
6. Connect battery cables to battery positive
and negative terminals and neutral wires on
the UPS cabinet.
M12x13.5 (8 PCS)
46 N•m
M12x13.5 (3 PCS)
46 N•m
10
5. Connect AC output power cables to the
output terminals N, U, V, and W on the UPS
cabinet.
M12x13.5 (4 PCS)
46 N•m
7. Route signal cables. Bind cables to the
cabinet. The figure shows the signal cables
routed from the top of the cabinet.

Advertisement

loading