Description of the device

2.3 PROFIBUS interface

2.3
PROFIBUS interface
PROFIBUS network
The physical link between the PROFIBUS interface and the PROFIBUS network is via a
floating RS-485 interface that is part of the module. Depending on the network configuration,
data rates of 9.6 Kbps up to a maximum of 12 Mbps are possible in the PROFIBUS network.
Note
You will find information about the structure of a PROFIBUS network in the system manual
"PROFIBUS Network Manual". The document is part of the Manual Collection. You will also
find this on the Product Support pages under the following entry ID:
35222591 (https://support.industry.siemens.com/cs/ww/en/view/35222591)
PIN assignment
The D-sub female connector has the following pin assignment:
PIN
Short name
1
NC
2
NC (M24)
3
LTG_B
4
RTSAS
5
M5EXT
6
P5EXT
7
NC (P24V)
8
LTG_A
12
Meaning
Socket pin 1 is not connected.
Socket pin 2 is not connected. With other MPI/DP components,
the return line of the floating 24 V power supply may be via this
pin.
Signal line B of the PROFIBUS connector.
RTSAS, input signal for direct MPI link. The control signal is "1"
active when the automation system connected over a special
MPI cable is sending.
M5EXT return line (GND) of the 5 V power supply. The current
load of an external consumer connected between P5EXT and
M5EXT must not exceed a maximum of 90 mA.
P5EXT supply (+5 V) of the 5 V power supply. The current load
of an external consumer connected between P5EXT and
M5EXT must not exceed a maximum of 90 mA (short-circuit
proof).
Socket pin 7 is not connected. With other MPI/DP components,
the P24V supply of the floating 24 V power supply may be via
this pin.
Signal line A of the PROFIBUS connector.
Operating Instructions, 08/2016, C79000-G8976-C301-02
Input/output
-
-
Input/output
Input
Output
Output
-
Input/output
CP 5613 A2/CP 5614 A2