Viessmann VITOCROSSAL 200 CM2 Service Instructions For Contractors page 44

400 to 620 kw gas condensing boiler with matrix cylinder burner, for open flue and room sealed operation, permissible operating pressure 6 bar
Hide thumbs Also See for VITOCROSSAL 200 CM2:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Detailed fault code for fault F Fd
Detailed fault code Component/signal
30
Reset button
31
Fuel valve 2 feedback
32
Air pressure switch 1
34
Gas pressure switch 1
35
Plug 41 demand T2
36
Plug 90 T8
37
Plug 90 T7
38
Fuel valve 1 feedback
3A
Ignition feedback
3B
Air pressure switch 2
60
Hall signal fan feedback
(RM-N)
44
Cause of fault
Programming unit faulty, wir-
ing
Incorrect return voltage (e.g.
DC voltage), actuator faulty
High switching sequence,
switch flutters, external volt-
age
High switching sequence,
switch flutters, external volt-
age
High switching sequence,
switch flutters, external volt-
age
High switching sequence,
switch flutters, external volt-
age
High switching sequence,
switch flutters, external volt-
age
Incorrect return voltage (e.g.
DC voltage), actuator faulty
Incorrect return voltage (e.g.
DC voltage), actuator faulty
High switching sequence,
switch flutters, external volt-
age
Fan speed too high. Incor-
rect fan or incorrect coding
card
Measure
Replace programming unit
Check wiring
Disconnect the plug from fuel
valve 2, reset the burner con-
trol unit and check the fault
messages.
If fault F Fd recurs, replace
burner control unit; otherwise
replace fuel valve 2.
Check flue gas path and com-
bustion. Check setting LDW1.
Check burner gauze assem-
bly for contamination.
Check the gas supply. Check
setting GDW1 and gas train
intake screen.
Check whether external volt-
age is present.
Check on-site connection.
Check whether external volt-
age is present.
Check on-site connection.
Check whether external volt-
age is present.
Check on-site connection.
Disconnect the plug from fuel
valve 1, reset the burner con-
trol unit and check the fault
messages.
If fault F Fd recurs, replace
burner control unit; otherwise
replace fuel valve 1.
Disconnect cable from igni-
tion module, reset burner
control unit and check the
fault messages.
If fault F FD recurs, replace
burner control unit; otherwise
replace ignition module.
Check flue gas path and re-
heating surfaces.
Check air pressure switch 2
setting.
Check the fan.
Check coding card.