Viessmann VITOCROSSAL 200 CM2 Service Instructions For Contractors page 22

400 to 620 kw gas condensing boiler with matrix cylinder burner, for open flue and room sealed operation, permissible operating pressure 6 bar
Hide thumbs Also See for VITOCROSSAL 200 CM2:
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking the CO
Gas type
CO
at
lower heating output
(0 %)
Natural gas K
upper heating output
(G25.3) NL only
(100 %)
lower heating output
(0 %)
Natural gas Lw (G27)
upper heating output
PL only
(100 %)
lower heating output
(0 %)
Natural gas S
upper heating output
(G25.1) HU only
(100 %)
lower heating output
(0 %)
CO
test at the upper heating output
2
1. Press
until the service indicator has counted up
to "100" (= 100 %).
2. Check the CO
content at the flue pipe. For per-
2
missible CO
content, see the table on page 21.
2
3. If the CO
content needs adjusting:
2
Remove cap
and turn setting screw
B
steps (Allen key 3 mm) until the CO
within the specified range:
Turning clockwise
Turning anti-clockwise
CO
test at the lower heating output
2
B
A
Fig. 18
22
content
(cont.)
2
content
2
in small
A
content is
2
CO
content drops
2
CO
content increases
2
Rated heating output in kW
400
1.6 - 2.0 %
1.6 - 2.0 %
7.3 - 9.7 %
7.3 - 9.7 %
Actual value at upper heating output minus
0.6 - 0.9 %
0.6 - 0.9 %
7.7 - 9.7 %
7.7 - 9.7 %
Actual value at upper heating output minus
0.6 - 0.9 %
0.6 - 0.9 %
9.8 - 10.9 %
9.8 - 10.9 %
Actual value at upper heating output minus
0.6 - 0.9 %
0.6 - 0.9 %
4. Record the actual value in the report (on
page 62).
Status
Service
S
Fig. 19
1. Press
until the service indicator has counted
down to "0" (lower heating output).
2. Check the CO
content at the flue pipe.
2
500
1.6 - 2.0 %
7.3 - 9.7 %
0.6 - 0.9 %
7.7 - 9.7 %
0.6 - 0.9 %
9.8 - 10.9 %
0.6 - 0.9 %
R
620