Viessmann VITOCROSSAL 200 CM2 Service Instructions For Contractors page 43

400 to 620 kw gas condensing boiler with matrix cylinder burner, for open flue and room sealed operation, permissible operating pressure 6 bar
Hide thumbs Also See for VITOCROSSAL 200 CM2:
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed fault
System characteristics
code
F F6
Gas pressure switch reports
no gas pressure.
F F7
Fan pressure is produced
during the air pressure switch
idle state check.
F F7
Air pressure switch contact is
not in the idle state
F F8
Flame tears off during opera-
tion
F F8
Flame tears off during opera-
tion
F F8
Flame tears off during opera-
tion
F F9
Fan not running; fan speed
not reached.
F F9
Status duration too long, fan
ramp-up
F F9
Fan speed deviation
F F9
No feedback from fan
F FA
Fan runs without demand;
burner control unit in a fault
state.
F Fb
Burner does not start.
Internal system faults
Internal system faults occur if a flawless program
sequence can no longer be guaranteed.
Shown on dis-
System characteristics
play
F E5, F EC,
Fault in burner control unit
F Ed, F EE,
area
F FF
F Fd
Fault in burner control unit
area
Cause
Gas shut-off valve closed;
gas pressure switch faulty;
multiple problems with gas
supply
Wind influence on fan
Air pressure switch faulty
Incorrect gas type selec-
ted
Burner gauze assembly
faulty
Combustion characteris-
tics not ideal
Fan faulty; cables are faul-
ty or broken
Internal fault; fan cannot
reach its set value.
Fan faulty, cable "
A"
a-Ö
faulty or broken. Check
cable "
A", check exter-
a-Ö
nal power supply, replace
cable or fan, remove for-
eign bodies.
Fan faulty, external fan
power supply not connec-
ted or faulty, cable "
A"
a-Ö
faulty or broken, fan
blocked (poss. by foreign
bodies)
Fan does not reach idle
state, cable "
a-Ö
A" faulty,
fan faulty, burner control
unit faulty
Excessive combustion
chamber pressure
(LDW2); condensate
backup or condensate
path blocked off
Cause
Internal system fault and
EMC
See the following table
Troubleshooting
Measures
Open the gas shut-off valve. Check
gas flow pressure. Replace gas fil-
ter if necessary. Reset burner con-
trol unit; replace gas train.
Check the flue draught (chimney).
Replace air pressure switch.
Select the gas type (see from
page 13)
Check burner gauze assembly; re-
place if damaged.
Adjust burner setting (see page 21
onwards)
Check cables and replace fan if
necessary.
Replace fan or burner control unit.
Check cable, replace cable "
or fan if necessary.
Check cable "
A", check exter-
a-Ö
nal power supply, replace cable or
fan, remove foreign body.
Fan subject to wind influence,
check flue outlet and fan, replace
cable "
a-Ö
A", replace fan, replace
burner control unit.
Check condensate drain and flue
gas path for blockages.
Measures
Reset the burner control unit. Re-
place the burner control unit if the
fault persists.
See the following table
A"
a-Ö
43