Battery Check At Power Off; Touchscreen Calibration - Baldor KPD007 Installation & Operating Manual

Hmi operator panel
Table of Contents

Advertisement

Battery Check at Power OFF

It is possible to check the battery status when the unit is turned off.
Press the SERVIN key while the unit is turned off, the FAULT led will blink for a
short time if the battery is good. If the LED doesn't blink, it means that battery
level is low.
Note: After a battery check, wait at least 20 seconds before rechecking the

Touchscreen Calibration

Standard calibration:
Emergency calibration:
This procedure can be used when it is not possible to recall Configuration Mode.
4-2 Operation
battery.
1.
Recall Configuration Mode.
2.
Touch the CLEAR key until a small round symbol appears at the top right
corner of the screen.
3.
Touch and hold the symbol until it moves to the lower left corner of the
screen.
Touch and hold the symbol until the indication to touch the ← key is
4.
displayed on the screen.
Touch and hold the key → until the indication to touch the ↑ key is
5.
displayed on the screen.
Touch and hold the key ↓ until the indication to touch the Enter key is
6.
displayed on the screen.
7.
Touch and hold the Enter key until the panel changes to the Operation
Mode (if a valid project is loaded in the memory).
1.
Turn the unit OFF.
2.
Turn the unit ON.
3.
Press the middle of the touchscreen once per second until the panel
changes to the Calibration Mode.
4.
Perform the standard calibration procedure.
MN1272

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kpd008Kpd009–501Kpd009–502