Service
Description
ICV Name
¡50
OD %
¡51
AI [mA]
¡52
AI [V]
AO [mA]
¡53
DI
¡54
¡55
DO Close
¡56
DO Open
¡57
DO Alarm
¡58
Display mP SW ver.
¡59
Motor mP SW ver.
Reset to factory setting:
1. Remove the power supply.
2. Activate down arrow and up arrow push buttons
at the same time.
3. Connect the power supply.
4. Release down arrow and up arrow push buttons.
5. When the display on ICAD (fig. 2) is alternating
between showing: CA and A1 the factory
resetting is complete.
© Danfoss A/S (AC-SMC/MWA), 08-2011
Min
Max
Factory
Stored
Unit Pass word Comments
Setting
0
100
-
0
100
-
0
100
-
0
100
-
0
1
-
0
1
-
0
1
-
0
1
-
0
100
-
0
100
-
DKRCI.PI.HV0.E6.02 / 520H3832
%
-
ICM valve Opening Degree
mA
-
AI signal
V
-
AI signal
mA
-
A0 signal
-
-
DI signals. Depending of ¡02
If ¡02 = 2, one digits are shown. See fig. 8
0 : DI1 = OFF
1 : DI1 = ON
If ¡02 = 3, two digits are shown. See fig. 9
00 : DI1 = OFF, DI2 = OFF
10 : DI1 = ON, DI2 = OFF
01 : DI1 = OFF, DI2 = ON
11 : DI1 = ON, DI2 = ON
-
-
DO Closed status. ON when OD < 3 %
-
-
DO Open status. ON when OD > 97 %
-
-
DO alarm status. ON when a Alarm is detected
-
-
Software version for display microprocessor
-
-
Software version for motor microprocessor
6