How To Place Ff Devices On The Foundation Fieldbus - Siemens SIMATIC PCS 7 FOUNDATION Fieldbus Commissioning Manual

Process control system
Table of Contents

Advertisement

6. Optional steps for redundant FOUNDATION Fieldbus:
These steps depend on the bus link that is used as the interface to PROFIBUS DP:
7. Click "OK".
The interface module (IM ...) is created with a FOUNDATION Fieldbus: FF subsystem.
5.2.2

How to place FF devices on the FOUNDATION Fieldbus

Setting/changing the device name for an FF device
The following applies to FF devices in a PCS 7 plant:
● The length of the device name is 32 characters (will be automatically filled with empty
spaces).
● The following characters are not permitted:
" & ? * < > | % § € ' . \ ] [
Use SIMATIC PDM to set the device name.
Requirements
● The following option has been enabled for at least one AS in SIMATIC Manager > SIMATIC
PDM Options > Settings:
Select type when device is inserted in HW Config
● The device descriptions of the required field devices are integrated in SIMATIC PDM.
FOUNDATION Fieldbus
Commissioning Manual, 02/2015, A5E32711026-AC
Step
FF Link
a
Select the IM 153‑2 FF.
b
Double-click on the slot of the first
"FDC 157" in the table.
The "Properties - Coupler" dialog box
opens.
c
Select the "Parameters" tab.
d
Select the redundancy mode in the "Value" column:
● No redundant configuration (default)
● Coupler redundancy
● Ring redundancy
Information
If you want to use ring redundancy, the "RING" DIP switch must be set to the "ON"
on the
position.
"RING" DIP
● OFF: Coupler redundancy or non-redundant configuration
switch
● ON: Ring redundancy
During operation, the position of the
"RING" DIP switch must match the
configuration of the FDC 157 for both
FDC 157 field device couplers.
Compact FF Link (IM 655-5 FF)
Select the IM 655-5 FF.
Double-click on the slot of the first "Field
Device Coupler" in the table.
The "Properties - Coupler" dialog box
opens.
During operation, the position of the
"RING" DIP switch must match the config‐
uration of the integrated field device cou‐
pler for both Compact FF Links.