Operation
IQ VVC-208 Control
SYSTEM PROGRAMMING (continued)
KEY PRESS
6
Set Temperature Mode
7
Program Setback Time
8
Program Setback Temperature
9
Set Hold Time
10
Set Hold Temperature
11
Set Hold Done
12
Set Hold Fan Speed
DISPLAY
TEMPERATURE
F = FAHRENHEIT or
C = CELSIUS
SETBACK TIME
HH:MM
SETBACK TEMP
xxx
HOLD TIME
HH:MM
HOLD TEMP
xxx
HOLD DONE
(AUTOMATIC, MANUAL)
HOLD FAN SPEED
(HIGH, LOW)
20
ACTION
•
Press the LEFT or RIGHT arrow
keys to select the method that
all temperatures will be dis-
played in.
•
Press the "P" key to lock in your
entry
•
Press the numbered prod-
uct keys to select the time in
HH:MM format for activating
Setback mode.
NOTE: 0:00 is default to disable
Setback.
•
Press the "P" key to lock in your
entry
•
Press the numbered product
keys to select the Setback
temperature in the range of
140-300°F.
•
Press the "P" key to lock in your
entry
•
Type in the length of hold time
required. The value is in the
range of 00:00 to 99:59.
•
Press the "P" key to advance to
the next stage or parameter.
•
Type in the desired Hold tem-
perature. Hold Temperature
Range is 140-210°F
•
Press the "P" key to advance to
the next stage or parameter.
•
Press the LEFT or RIGHT arrow
keys to select Hold Done.
•
Press the "P" key to advance to
the next stage or parameter.
•
Press the LEFT or RIGHT arrow
keys to select Hold Fan Speed.
•
Press the "P" key to advance to
the next stage or parameter.