Cleanness; Emi; Laser Safety - H3C S5820X Series Installation Manual

Hide thumbs Also See for S5820X Series:
Table of Contents

Advertisement

For the temperature and humidity requirements of different switch models, see

Cleanness

Dust buildup on the chassis may result in electrostatic adsorption, which causes poor contact of metal
components and contact points, especially when indoor relative humidity is low. In the worst case,
electrostatic adsorption can cause communication failure.
Table 20 Dust concentration limit in the equipment room
Substance
Dust
NOTE:
The dust diameter is greater than or equal to 5 μm.
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in
Table 21 Harmful gas limits in the equipment room
Gas
SO
2
H
S
2
NH
3
Cl
2

EMI

All electromagnetic interference (EMI) sources, from outside or inside of the switch and application
system, adversely affect the switch in a conduction pattern of capacitance coupling, inductance coupling,
electromagnetic wave radiation, or common impedance (including the grounding system) coupling. To
prevent EMI, take the following actions:
Use a single-phase three-wire power receptacle with a protection earth (PE) to filter interference
from the power grid.
Keep the switch far away from radio transmitting stations, radar stations, and high-frequency
devices.
Use electromagnetic shielding, for example, shielded interface cables, when necessary.
Route interface cables only indoors to prevent signal ports from getting damaged by over-voltage
or over-current caused by lightning strikes.

Laser safety

The H3C S5820X Switch Series is a line of Class 1 laser devices.
Concentration limit (particles/m³)
≤ 3 x 10
4
(no visible dust on the tabletop over three days)
Table
25
21.
Maximum concentration (mg/m
0.2
0.006
0.05
0.01
Table
1.
)
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5820x-28sS5820x-26sS5820x-28c

Table of Contents