6. Checklist for installing HVI
If all questions in the below checklist are answered with "yes", it can be assumed that the
HVI
long Conductors is installed correctly. A pdf file of the checklist can be downloaded at
®
http://www.dehn.de.
Checklist for HVI
Address of the test object:
Name _____________________________________________________________________________________
Contact partner ______________________________________________________________________________
Postcode, Place, Street _________________________________________________________________________
Phone _____________________________________________________________________________________
Item
1
Is the whole system positioned in the protected area of the isolated air-termination
system?
2
Has the separation distance been calculated?
(down conductor to the earth-termination system, isolated system with connec-
tion to existing external lightning protection system or lightning equipotential
bonding on roof level)
3
Is the maximum equivalent separation distance specified by DEHN + SÖHNE for
the application of the HVI
HVI
®
HVI
®
HVI
®
4
Is the calculated separation distance kept in the range of the sealing end?
5
Is the supporting tube and, if required, the equipotential bonding element of the
sealing end correct, i.e. only connected with the equipotential bonding / the light-
ning equipotential bonding of the system?
6
Is the minimum distance of 0.2 m kept between HVI
lel and has the connection to opposite down conductors been considered?
7
Has the minimum bending radius been kept?
HVI
HVI
HVI
HVI
8
Is the equipotential bonding element of the sealing end in contact with the semi-
conductive layer (not grey coating)?
9
Has the supplementary information of the DEHN installation instructions No. 1501
been considered for the installation of the HVI
__________________________________
______________________________________________________________
Figure 18 Check list
22
Installation
®
Question
®
Conductor kept?
light Conductor / DEHNcon H
s ≤ 0.45 m in air
Conductor
s ≤ 0.75 m in air
power Conductor
s ≤ 0.9 m in air
light Conductor (dark grey outer coating)
®
®
Conductor (black outer coating)
Conductor (grey outer coating)
®
®
power Conductor (black outer coating)
_________________________
Place
Signature of tester
Condcutors
®
s ≤ 0.9 m solid material
s ≤ 1.5 m solid material
s ≤ 1.8 m solid material
Conductors routed in paral-
®
200 mm
200 mm
230 mm
270 mm
Conductor in hazardous areas?
®
Company
Date
Rating
YES
NO