dehn HVI Series Installation Instructions Manual page 35

Long conductors insede/outside the supporting tube
Hide thumbs Also See for HVI Series:
Table of Contents

Advertisement

Available languages

Available languages

As-delivered condition
air-termination rod
Ø 22/16/10 mm
air-termination tip
Ø 10 mm
locking screws
tightening torque of 15 Nm
-air-termination tip 2x M8x16 mm
-air-termination rod 2x M8x10 mm
locking screw
head piece
(M8 x 25 mm,
tightening torque of 15 Nm)
GRP/Al supporting tube
HVI
Figure 4 Installation of the head piece in the supporting tube
long Conductor
®
Assembled
condition
Correct
assembly
head of the supporting tube
water-proof
locking screw
head piece, M8 x 25 mm,
tightening torque of 15 Nm
Incorrect
assembly
approx. 13 mm approx. 0 mm
approx.7 mm
11