Technical Data
Environment
Operational ambient temperature range
Enclosed Drives:
Storage ambient temperature range: -40 ... 60°C
Maximum altitude:
Maximum humidity:
Rating Tables
Frame
kW
Size
110 - 115 (+ / - 10%) V 1 Phase Input, 230V 3 Phase Output (Voltage Doubler)
1
0.37
1
0.75
2
1. 1
200 - 240 (+ / - 10%) V 1 Phase Input, 3 Phase Output
1
0.37
1
0.75
1
1.5
2
1.5
2
2.2
3
4
200 - 240 (+ / - 10%) V 3 Phase Input, 3 Phase Output
1
0.37
1
0.75
1
1.5
2
1.5
2
2.2
3
4
3
5.5
4
7.5
4
1 1
380 - 480 (+ / - 10%)V 3 Phase Input, 3 Phase Output
1
0.75
1
1.5
2
1.5
2
2.2
2
4
3
5.5
3
7.5
3
1 1
4
15
4
18.5
4
22
NOTE Cable sizes shown are the maximum possible that may be connected to the drive. Cables should be selected
according to local wiring codes or regulations at the point of installation.
-20 ... 40°C (frost and condensation free)
2000m. Derate above 1000m: 1% / 100m
95%, non-condensing
HP
Input
Fuse/MCB
Current
Non UL
0.5
7.8
10
1
15.8
25
1.5
21.9
32
0.5
3.7
10
1
7.5
10
2
12.9
16
2
12.9
16
3
19.2
25
5
29.2
40
0.5
3.4
6
1
5.6
10
2
8.9
16
2
8.9
16
3
12. 1
16
5
20.9
32
7.5
26.4
40
10
33.3
40
15
50. 1
63
1
3.5
6
2
5.6
10
2
5.6
10
3
7.5
16
5
1 1.5
16
7.5
17.2
25
10
21.2
32
15
27.5
40
20
34.2
40
25
44. 1
50
30
51.9
63
Maximum Cable
(Type B)
UL
mm
10
8
20
8
30
8
6
8
10
8
17.5
8
17.5
8
25
8
40
8
6
8
10
8
15
8
15
8
17.5
8
30
8
35
8
45
16
70
16
6
8
10
8
10
8
10
8
15
8
25
8
30
8
35
8
45
16
60
16
70
16
Output
Size
Current
AWG
A
8
2.3
8
4.3
8
5.8
8
2.3
8
4.3
8
7
8
7
8
10.5
8
15.3
8
2.3
8
4.3
8
7
8
7
8
10.5
8
18
8
24
5
30
5
46
8
2.2
8
4. 1
8
4. 1
8
5.8
8
9.5
8
14
8
18
8
24
5
30
5
39
5
46
Recommended
Brake Resistance
Ω
-
-
100
-
-
-
100
50
25
-
-
-
100
50
25
20
15
10
-
-
250
200
120
100
80
50
30
22
22