FCC USA
● For article number 6GK1 411-6CA40-0AA0: FCC ID: SJC-M2140
● For article number 6GK1 411-6CA40-0BA0: FCC ID: LYH-IEWSNPA1
Canada
IC Canada
● For article number 6GK1 411-6CA40-0AA0: IC ID: 5853A-M2140
● For article number 6GK1 411-6CA40-0BA0: IC ID: 267AA-IEWSNPA1
Ordinary Location Certification for FM
As standard, the Link has been examined and tested to determine that the design meets basic electrical, mechanical, and
fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
FM certification (explosion protection)
NEMA TYPE 4X
TEMP CODE T4
(Tamb = -40 °C TO 60 °C)
FM Division 2, Non-Incendive
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
Dust Ignition-proof for Class II, III, Division 1,
Groups E, F, and G; Indoors/outdoor locations;
NEMA Type 4X
Temperature code: T4 (T
CSA HAZ LOC. (Canadian Standards Association, Hazardous Locations)
TYPE 4X
TEMP CODE T4
CSA Division 2, Non-Incendive
Suitable for Class I, Division 2, Groups A, B, C, and D.
Dust Ignition-proof for Class II, Groups E, F, and G;
Suitable for Class III Hazardous Locations.;
Install per Siemens drawing A5E02467236A.
Temperature code: T4 (T
CSA Enclosure Type 4X
CSA certificate of compliance
2165440 (April 27, 2009)