  • Page 1 REMKO SLN 40-80 Swimming pool dehumidifier Operation · Technology · Spare parts Edition GB – T08...
  • Page 3: Table Of Contents

    Safety information Unit description Installation Commissioning Care and maintenance Troubleshooting Refrigeration circuit Electrical wiring diagrams SLN 40-80 Intended use Customer service and warranty Environmental protection and recycling Diagram of unit SLN 40-80 Spare parts list SLN 40-80 Maintenance log Technical data...
  • Page 4: Dehumidification

    REMKO SLN 40-80 Dehumidification The interrelated processes occur- In terms of energy consumption, ring during dehumidification are dehumidification has one decisive based on physical laws. advantage: These are illustrated here in sim- plified form in order to explain the Energy expenditure is restricted principle of dehumidification.
  • Page 5 90-190 l/m³, heavy through the REMKO dehumidi- same and the relative humidity concrete 140-190 l/m³, lime-sand fier. It is dehumidified and lea- increases.
  • Page 6: Safety Information

    REMKO SLN 40-80 Heat of condensation the liquefaction of gas, which is The supplied air during dehumidi- The energy transferred from the condenser to the air is composed termed heat of condensation. fication creates a large amount of heat energy, which is expressed in The amount of heat of evaporation a rise of temperature.
  • Page 7: Unit Description

    60% relative humidity. avoided. The respective unit function is shown on the front display. The recirculation fan sucks in the humid room air via the lower duct Functional diagram of SLN 40-80 dehumidifier Adjacent Heated and room dehumidified air REMKO...
  • Page 8: Installation

    REMKO SLN 40-80 Installation For optimal and reliable unit op- Prior to joining the duct connec- The duct section with filter in ■ ■ eration, the following information tions, the wall connections must the lower duct opening where must be observed in any event:...
  • Page 9 Connection to the duct connec- The room to be dehumidified Condensate drain ■ ■ tion already installed in the wall must be closed from the ambi- takes place with the self-sealing ent atmosphere. The condensate drain is located at profile lips located on the unit the bottom of the unit.
  • Page 10: Commissioning

    REMKO SLN 40-80 Commissioning Prior to each commissioning or as LED display required, the air inlet and outlet grille must be checked for clog- ging. A constant „green“ lightning The units operate via an integrated symbol indicates that the supply is...
  • Page 11: Care And Maintenance

    Care and maintenance Fan control Cleaning the suction filter NOTE Regular care and maintenance When the hygrostat starts the The suction filter should be is a basic precondition for a dehumidifier, the fan(s) is/are checked at regular intervals and long useful life and trouble- switched on together with the cleaned if necessary.
  • Page 12: Troubleshooting

    REMKO SLN 40-80 Troubleshooting Fault Possible cause Remedy • The unit does not start. No supply voltage. • Check supply connection and local fuses or switches. • Lightning symbol in display does not light. • The unit does not start.
  • Page 13: Refrigeration Circuit

    Refrigeration circuit SLN 40 Legend: 1. Compressor 2. Evaporator 3. Condenser 4. Thermal expansion valve 5. Dry filter 6. Solenoid valve 7. Fan SLN 60 und SLN 80 Legend: 1. Compressor 2. Evaporator 3. Condenser 4. Thermal expansion valve 5. Dry filter 6.
  • Page 14 REMKO SLN 40-80 Electrical wiring diagram SLN 40 - SLN 80 Electronic control board Fan motors: SLN 40 = Motor M2 SLN 60 = Motor M2 and M3 SLN 80 = Motor M2 M3 and M4 Legend: Constant ventilation: External hygrostat:...
  • Page 15: Intended Use

    The units are operated with en- recyclable. REMKO GmbH & Co. KG. vironmentally-friendly and ozone neutral refrigerant R407C. Make your contribution towards In accordance with legal and...
  • Page 16: Diagram Of Unit Sln

    REMKO SLN 40-80 Diagram of unit SLN 40 - 80 Fig. REMKO SLN 80 We reserve the right to make dimensional and design changes in the interest of technical advances.
  • Page 17: Spare Parts List Sln

    Spare parts list Designation SLN 40 SLN 60 SLN 80 EDP No. EDP No. EDP No. Wall bracket 1109144 1109165 1109177 Housing rear 1109188 1109189 1109190 Cable gland 1109129 1109129 1109129 Condenser 1109146 1109167 1109179 Fan complete with 80mm cable...
  • Page 18: Maintenance Log

    REMKO SLN 40-80 ✍ Maintenance log Model: ........Serial No.: ........10 11 12 13 14 15 16 17 18 19 20 Unit cleaned – externally Unit cleaned – internally Condenser cleaned Evaporator cleaned Fan function checked Unit checked for damage...
  • Page 19: Technical Data

    Technical Data Series SLN 40 SLN 60 SLN 80 Daily dehumidification capacity at 30°C and 80% Litre/day 50.4 70.8 100.8 relative humidity Daily dehumidification capacity at 30°C and 60% Litre/day 32.2 43.2 64.0 relative humidity Operating temperature range °C 10 to36 Humidity operating range % rel.
  • Page 20 REMKO, a partner that helps solve problems. Sales REMKO not only provides an extensive sales network in Germany and abroad, but also unusually highly qualified sales experts. REMKO sales representatives are more...