EPSITRON®
787-1668 Electronic Circuit Breaker
Pos : 57 /Serie 787 (EPSITRON)/F unkti ons besc hrei bung/Digital eingang S1 787- 1668 @ 12\mod_1341908222413_21.doc x @ 99460 @ 233 @ 1
6.6
Control Input S1
A signal between S1 and 0 V has the effect that
•
all channels previously de-activated due to overloading can now be re-
activated.
•
specific channels can be activated or de-activated.
6.6.1
Re-activating Tripped Channels
Apply a signal for at least 0.5 seconds. All channels previously de-activated due
to overloading are then re-activated in sequential order, based on the load applied.
Figure 18: Example of re-activation via control input S1, or signal output S3.
Manual
Version 1.1.0
Function Description
37