6.5
ON Delay for Specific Channels
The outputs are activated in a staggered manner in the order of their channel
numbers as soon as a minimum input voltage is present. Outputs which have been
de-activated manually, or by a reset signal, are skipped in this process.
The time at which the next output in the sequence is activated is based on the
following conditions:
•
At least 50 ms must elapse after activation of the previous output.
•
The output current of the previously activated output must lie below the
nominal value set for the output.