Function Description
Pos : 55 /Serie 787 (EPSITRON)/F unkti ons besc hrei bung/Z usc haltverz ögerung 787-166x @ 12\mod_1341479703716_21.doc x @ 98963 @ 2 @ 1
6.5

ON Delay for Specific Channels

The outputs are activated in a staggered manner in the order of their channel
numbers as soon as a minimum input voltage is present. Outputs which have been
de-activated manually, or by a reset signal, are skipped in this process.
The time at which the next output in the sequence is activated is based on the
following conditions:
At least 50 ms must elapse after activation of the previous output.
The output current of the previously activated output must lie below the
nominal value set for the output.