Response Of The Electronic Circuit Breaker With Active Current Limitation - WAGO EPSITRON 787-1668 Series Manual

Electronic circuit breaker 24 vdc, 8 x 2...10 a
Table of Contents

Advertisement

EPSITRON®
787-1668 Electronic Circuit Breaker
6.2.3.1
Response of the Electronic Circuit Breaker with Active Current
Limitation
Nominal
current
0.5 A
1 A
2 A
3 A
4 A
6 A
The function is activated when
an over-current measured at an output is greater than the corresponding
threshold for the set nominal current (Threshold 1).
the measured over-current is present for more than 0.1 ms.
The activated circuit breaker can respond in one of three ways:
1.
An over-current is present that is greater than Threshold 3
2.
An over-current is present that is greater than Threshold 1,
but less than Threshold 2
3.
An over-current is present that is greater than the nominal current, but less
than Threshold 1
Manual
Version 1.1.0
after 5 seconds,
with an over-current greater than
(Threshold 1)
0.75 A
1.20 A
2.20 A
3.30 A
4.40 A
6.60 A
Function Description
Shutdown takes place
within 50 milliseconds ... 5 seconds,
with an over-current between
(Threshold 2)
1.00 A
1.50 A
3.00 A
4.50 A
6.00 A
8.00 A
31
(Threshold 3)
1.20 A
1.70 A
3.40 A
5.10 A
6.80 A
10.2 A