Specification - ABB C505 User Manual

Control it 1/2 din advanced process controller, industrial it enabled
Table of Contents

Advertisement

SPECIFICATION

Summary
17 application templates: Single loop, Cascade,
Feedforward, Ratio, Auto/Manual
Two Autotune options
Control Efficiency Monitor
PC configuration
IP66/NEMA4X front face
Operation
Display
2 x 100mm 40-segment LED bargraphs
2 x 10mm 4-digit LED indicators
1 x 10mm 3-digit LED indicators
Display range
–1999 to +9999
Configuration
Basic configuration via front panel keys
Advanced feature configuration by PC only
Security
Internal security switch and password-protected menus
90
Standard Functions
Control Strategies
Single-loop, Auto/Manual Station, Analog Backup, Indicator/
Manual Loader, Cascade, Feedforward, Ratio
Output Types
Current proportioning, Time proportioning, On/off, Motorized valve
(with and without feedback), Heat/cool.
Control Parameters
Four sets of PID settings, selectable via digital signals
Set Points
Local, remote and four local set points, selectable via digital
signals
Configured Outputs
Three preset output values, selectable via digital signals
Autotune
On demand for
1
/
wave or minimal overshoot
4
Process Alarms
Number
8
Types
High/low process, High/low output,
High/low deviation
Hysteresis
Level and time *
Alarm enable/disable
Enable/disable of alarms via digital signal
Real Time Alarms *
Number
2
Programmable
On time/day and duration
* Accessed via PC Configurator

Advertisement