ABB C505 User Manual page 45

Control it 1/2 din advanced process controller, industrial it enabled
Table of Contents

Advertisement

3.3 Level 3 – Set Points
Note. Level 3 is not applicable if Auto/Manual Station or Indicator templates are selected.
3. 0 0
LEV. 3
SEtP
•1
3. 0 1
LSP1
500
•1
3. 0 2
LSP2
•2
200
•1
3. 0 4
LSP4
•2
400
•3
3. 0 5
S. S Pt
300
•4
3. 0 6
rAtO
1. 0 00
•4
3. 0 7
BIAS
0
•1
Not displayed for ratio controller or ratio station templates.
•2 Displayed only if a local set point source is selected – see Section 4.5/ Set Point Configuration/ Local/Remote
Set Point Source.
•3
Only displayed if a cascade template is selected.
•4
Displayed only for templates with a remote set point.
Level 3 – Set Points
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Local Set Point Value 1
Set the default local set point value.
[Within set point high and low limits, in engineering units – see Level 9]
Local Set Point Values 2 to 4
[Within set point high and low limits, in engineering units – see Level 9]
Cascade Slave Set Point Value
Set the slave set point value.
[Within slave set point high and low limits, in engineering units]
Only adjustable in Manual mode.
Remote Set Point Ratio
The remote set point value is
(ratio x remote set point input) + bias.
[0.001 to 9.999]
Remote Set Point Bias
[In engineering units]
Continued...
3 SET UP MODE...
3.00...3.07