...4.10 Level E – Calibration
FCAL
MAN
•1
E11
Fb. L O
100. 0
•1
E. 1 2
Fb. H I
500. 0
rEF
2700
FCAL
NO
O. C AL
NO
Fb. H I
500
E. 1 3
rEF
2700
E. 1 4
bEtA
3977
E. 1 5
CJ1
25. 2
•2
E. 1 6
CJ3
•3
25. 2
LEV. E
CAL
•1
Only displayed if Motorized Valve with feedback output type is selected – see Section 4.2, Basic Configuration.
•2
Only displayed if corresponding input type is set to 'THC'.
•3
Only displayed if option board is fitted.
Position Feedback Electrical Range Low
Set the minimum electrical input value.
[0.0 to 999.9]
For resistance input types, no decimal places are displayed. For all other
input types, 1 decimal place is displayed.
Position Feedback Electrical Range High
Set the maximum electrical input value.
[0.0 to 999.9]
Continued in
Cold Junction Reference Value
Cold Junction Reference Value
This value should only be changed if a new CJ sensor is supplied with a CJ
reference value different to 2700.
The resistance (in Ohms) of the CJ sensor at 25°C.
Cold Junction Beta Value
This value should only be changed if a new CJ sensor is supplied with a CJ
Beta value different to 3977.
The beta value of the CJ sensor.
Cold Junction Reading – I/P1 and I/P2
The temperature measured by the cold junction sensor is displayed in °C.
Cold Junction Reading – I/P3
The temperature measured by the cold junction sensor is displayed in °C.
Return to top of Calibration Level.
4 CONFIGURATION MODE...
frame.
E.11...E.16
79