Table of Contents

Advertisement

Connectable components
9.1 NX10/15
9.1.4

Connection

Power supply X124
Table 9- 3
Pin assignment for X124
Terminal
+
+
G
G
Note
The two "+" and "G" terminals are jumpered in the connector and not in the device. This
ensures that the supply voltage is looped through.
The current consumption increases by the current consumption of DRIVE-CLiQ and the
digital outputs.
When using external power supplies (e.g. SITOP), the ground potential must be connected
with the protective ground terminal (PELV).
Table 9- 4
Characteristics
Connector type
Connection option
Max. current carrying capacity incl. loop-through
Maximum power consumption
Max. cable length
DRIVE-CLiQ interfaces X100 - X103
Table 9- 5
Characteristic
Connector type
Cable type
Max. cable length
90
Function
24 V DC power supply (20.4 V - 28.8 V)
Ground
Cable specifications for X124
Characteristics of X100 - X103
Version
DRIVE-CLiQ plug
DRIVE-CLiQ standard (inside the control cabinet)
MOTION CONNECT (outside the control cabinet)
70 m
Version
Screw-type terminals
Up to 2.5 mm
2
20 A
0.8 A (without load)
10 m