INSTALLATION INSTRUCTIONS
IMPORTANT: READ ALL INSTRUCTIONS THOROUGHLY AND CAREFULLY PRIOR TO INSTALLATION OF LINEAR
SERIES FIXTURES AND RETAIN FOR FUTURE REFERENCE.
3.
HARDWIRED FIXTURES (LNK):
REMOVE LED LIGHT COVER, SEE "REMOVING LED LIGHT COVER (FXT AND LNK)" IN THIS INSTRUCTION.
TAKE NOTE WHERE DRIVER IS LOCATED IN LED CHASSIS.
CHOOSE A SUITABLE KNOCKOUT LOCATION FROM THOSE PROVIDED IN FIXTURE HOUSING.
REMOVE THE KNOCKOUT WITH A SCREWDRIVER.
PULL EXISTING AC POWER FROM BUILDING THROUGH KNOCKOUT LOCATION INTO FIXTURE HOUSING. PROVIDE UL APPROVED STRAIN RELIEF (NOT
PROVIDED) AS REQUIRED.
4.
MAKE ELECTRICAL CONNECTIONS PER ALL APPLICABLE CODES:
NORMAL POWER WIRING - BLACK TO BLACK (HOT); WHITE TO WHITE (NEUTRAL) AND GREEN (OR BARE) TO GREEN (GROUND). ENSURE NO BARE WIRES
(OTHER THAN GROUND) ARE EXPOSED.
DIMMING WIRING – VIOLET TO VIOLET (DIM +); GREY TO GREY (DIM -).
LNK FIXTURE WIRING HARNESS DOES NOT EXTEND EMB SUPPLY WIRE. THIS MUST BE SUPPLIED BY AND RUN BY A QUALIFIED LOCAL ELECTRICAN TO
FIXTURE WITH EMB DRIVER IF IT IS NOT THE POWER DROP FIXTURE.
EMERGENCY WIRING (WITH SWITCH LEG) - BLACK TO BLACK (HOT); BLACK TO BLACK/RED STRIPE (SWITCH); WHITE TO WHITE (NEUTRAL) AND GREEN (OR
BARE) TO GREEN (GROUND). ENSURE NO BARE WIRES ARE EXPOSED.
EMERGENCY WIRING (WITHOUT SWITCH LEG) - BLACK TO BLACK (HOT) AND BLACK TO BLACK/RED STRIPE (SWITCH) (SAME CONNECTOR); WHITE TO
WHITE (NEUTRAL) AND GREEN (OR BARE) TO GREEN (GROUND). ENSURE NO BARE WIRES ARE EXPOSED.
IF WIRING EMB WITH WIRING THROUGH MULTIPLE FIXTURES (CONTINUOUS RUN), MAX AMBIENT ON ALL FIXTURES IS 40°C.
5.
ELECTRICALLY ATTACH LED LIGHT COVER TO FIXTURE HOUSING USING THE QUICK CONNECTOR. NEATLY ARRANGE THE WIRES AND ENSURE ALL THE WIRES
AND CONNECTIONS ARE SEALED PROPERLY INSIDE THE FIXTURE HOUSING. TAKE CARE NOT TO PINCH ANY WIRES.
6.
ATTACH LED LIGHT COVER BY RAISING IT TO THE CHASSIS AND SNAPPING IN PLACE.
7.
INSERT SAFETY SCREWS (PROVIDED).
8.
REMOVE PLASTIC FILM FROM LENS.
9.
TURN ON ELECTRICITY AT THE CIRCUIT BREAKER, PANELBOARD, OR FUSE BOX.
HARDWIRED FIXTURES (LNK), CONT.:
10. (LNK) LINKING SECTIONS TOGETHER:
EACH LNK FIXTURE COMES WITH THE MECJHANICAL JOINING PIECE (LS-MJP) INSTALLED ON ONE END FOR MECHANICAL CONNECTION.