Output - Siemens SITOP Series Operating Instructions Manual

Hide thumbs Also See for SITOP Series:
Table of Contents

Advertisement

Technical data

6.2 Output

Figure 6-1
6.2
Output
Output
Rated voltage value Ua rated DC
Total tolerance, static ±
Static line regulation, approx.
Static load regulation, approx.
Residual ripple in the load range
Peak-peak, max.
Spikes peak-peak, max. (bandwidth,
approx. 20 MHz)
Adjustment range
Product function / output voltage can be
adjusted
Output voltage setting
Remark
Status indicator
Signaling
Response when switching on/off
Starting delay, max.
Voltage rise, typ.
Voltage rise time of the output voltage,
maximum
Rated current value Ia rated
32
Power-failure buffering
6EP3333-8SB00-0AY0
(24 V/5 A)
Regulated, isolated DC voltage
24 V
3 %
0.03%
0.2%
50 mV
200 mV
24 to 28.8 V
Yes
Via potentiometer
Max. 120 W
LED green for 24 V O.K
Relay contact (NO contact, contact rating 60 V DC / 0.3 A) for 24 V O.K.
Overshoot of Ua approx. 3%
1 s
30 ms
500 ms
5 A
6EP3334-8SB00-0AY0
(24 V/10 A)
Regulated, isolated DC voltage
24 V
3 %
0.05%
0.3%
50 mV
200 mV
24 to 28.8 V
Yes
Via potentiometer
Max. 240 W
LED green for 24 V O.K
Overshoot of Ua approx. 3%
1 s
70 ms
500 ms
10 A
Operating Instructions, 06.2014, C98130-A7633-A1-2-7629