Removing The Burner And Checking The Burner Gasket (Replace Gasket Every Two Years) - Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
The flue pipe is deemed to be sound if
the CO
concentration in the combus-
2
tion air is no higher than 0.2 % or the
O
concentration is at least 20.6 %.
2
Removing the burner and checking the burner gasket
(replace gasket every two years)
1. Switch OFF the main power supply
and the ON/OFF switch at the con-
trol unit.
2. Close the gas shut-off valve and
safeguard against reopening.
3. Pull electrical cables from fan
motor A, gas valve B, ionisation
electrode C, ignition unit D and
earth tab E.
36
(cont.)
If actual CO
values are higher or O
2
values are lower, then pressure test
the flue pipe with a static pressure of
200 Pa.
4. Undo the fixing screws of gas con-
nection flange F.
5. Release four nuts G and remove
the burner.
!
Please note
Prevent damage to the wire
gauze.
Never rest the burner on the
gauze assembly.