Commissioning, inspection, maintenance
Further details regarding the individual steps
Maximum flow rate FX
Delivered condition: FX 3.0
Setting
Description
range
FX 0.0
FX
Select the flow rate in accordance with the installed collectors
20.0
(see Vitosol service instructions)
Heat transfer medium ME
Delivered condition: ME 1 (never adjust)
Setting
Description
range
ME 0
Water
ME 1
Tyfocor G-LS
Manual mode MM
Delivered condition: MM 4 (automatic mode)
Setting
Description
range
MM 0
Relay 1 and 2 OFF
MM 1
Relay 1 (solar circuit pump) ON, relay 2 OFF
MM 2
Relay 1 (solar circuit pump) OFF, relay 2 ON
MM 3
Relay 1 (solar circuit pump) ON, relay 2 ON
MM 4
Automatic mode
Instructing the system user
The system installer must hand the operating instructions to the system user
and instruct him/her in the operation of the system.
Scanning and resetting the "Service" display
The red fault indicator flashes when the limits set via coding address "21" and
"23" have been reached. "Service" flashes in the programming unit display:
64
3.0 l/min
(cont.)