Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual page 96

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
dA
Control mode with-
out room influence
db
Control mode with-
out room influence
dd
Control mode with-
out room influence
dE
Control mode with-
out room influence
E4
Burner blocked
E5
Burner blocked
E8
Burner in a fault
state
E9
Burner in a fault
state
96
Cause
Measures
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit A1
circuit A1.
shorted out
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit with
circuit with mixer M2.
mixer M2 shorted
out
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit A1 lead
circuit A1 and the re-
broken
mote control DIP switch
settings (see page 126)
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit with
circuit with mixer M2
mixer M2 lead
and the remote control
broken
DIP switch settings (see
page 126)
Internal fault
Replace the control unit.
Internal fault
Check the ionisation
electrode and cables.
Check the flue gas sys-
tem for soundness.
Press "E RESET"; re-
place the control unit, if
required.
The ionisation
Check the ionisation
current lies out-
electrode and cable.
side the permissi-
Press "E RESET".
ble range
The ionisation
Check the ionisation
current lies out-
electrode and cable.
side the permissi-
Press "E RESET".
ble range during
calibration