Viessmann VITODENS 343-F WS4A Installation And Service Instructions Manual page 98

Compact energy tower with a gas fired condensing boiler as compact model; natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
F4
Burner in a fault
state
F8
Burner in a fault
state
F9
Burner in a fault
state
FA
Burner in a fault
state
FC
Burner in a fault
state
Fd
Burner in a fault
state
98
Cause
Measures
No flame signal.
Check the ionisation
electrode and cable,
measure the ionisation
current, check the gas
pressure, check the gas
train, ignition, ignition
module, ignition electro-
des and the condensate
drain.
Press "E RESET".
The fuel valve
Check the gas train.
closes too late.
Check both control
paths.
Press "E RESET".
Fan speed too
Check the fan, check
low during the
the fan cables and sup-
burner start
ply; check the fan con-
trol.
Press "E RESET".
Fan not at stand-
Check the fan, fan con-
still
necting cables and fan
control.
Press "E RESET".
Gas train faulty or
Check the gas train.
faulty modulation
Check the flue gas sys-
valve control; or
tem.
flue gas path
Press "E RESET".
blocked
Faulty burner
Check ignition electro-
control unit or
des and connecting
boiler coding card
cables.
Press "E RESET".
If the fault cannot be re-
moved, check the boiler
coding card or replace it,
if required, or replace
the control unit.