Installation
HP
Volts
Phase
2
208-230*
1
2
208-230*
3
3
208-230*
3
3
380-415
3
5
208-230*
3
5
380-415
3
5
575
3
*Figures represent maximum length in feet for 220 or 230 volt system. Use 75% of length for 208 volt system.
Branch Ckt.
Protection
Service
Locked
Factor
Rotor
Cur.
Cur.
Fusetron
(Amps)
(Amps)
(Amps)
12.0
61.0
20
7.2
45.0
15
10.5
62.0
15
5.4
29.0
15
17.2
92.0
25
8.8
49.0
15
7.0
37.0
15
Starting the System and Completing the Installation
Table D.
Wire Size for Max. Length of Run Shown
Ckt.
Brkr.
(From Service Entrance to Pump in Feet)
(Amps)
No. 14
No. 12
20
172
274
15
361
574
20
255
406
15
787
1250
30
---
240
15
472
750
15
929
1477
18
No. 10
No. 8
No. 6
929
673
1048
899
1410
2197
635
997
1552
1956
3070
---
376
590
920
1173
1841
2867
2311
3627
---
Nema
Codes
H
K
K
K
J
G
K