Viessmann EVO-COOL Series Installation And Operating Instructions Manual page 19

Refrigeration units
Table of Contents

Advertisement

Submenu 1
Fan
max. 100%
1
5
Temperature
1
5
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regar-
ding a certain purpose always require a special written agreement.
Page 55 GB
Submenu 2
Values
Drain down
0 min to 10 min
time
Drain line
heater acti-
vation pre
0 minto 10 min
defrost
Drain pre heat
Freezing
Yes / No
temperature
Back
Standard
Fan type
Eco-Linear
Pr. Evap.
0 min to 10 min
Sub. Evap.
0 min to 10 min
Start Evap.
-20°C to 10°C
Min. value v.
Temp Step 1
temp. intervals
of 5 to max. 50°C
min. 0°C to max.
Temp Step 5
value v. temp 5
min. value v
Rotary speed 1
rotary speed 5 to
max 100%
min. 0% to max.
Rotary speed 5
value v. rotary
speed 5
Back
Presetting
Description
CS Cooler
FS Freezer
After the defrosting process, a
waiting time is applied until the
normal operating mode (cool-
ing) is returned. In the case of
3 min
3 min
hot gas defrosting, the compres-
sor downtime runs concurrently.
I. e. the cooling operation can
only start after elapsing of this
time.
Lead time for the drain line.
Starts prior to the start of the
defrosting process. Thus, the
3 min
3 min
defrosting water does not drip
on the cold dripping tray and in
the cold drain hose.
Displays the temperature before
defrosting began in the data
Yes
Yes
logger during defrosting and
prevents temperature peaks
during defrosting.
– Activation of the fan with 230
V and the control output 0-10
V linear.
– Activation with a straight line
through the defined points
temperature 5 / speed 5 (lower
point) and temperature 1 /
speed 1 (upper point).
Delays the start-up of the evapo-
rator fan together with the start
3
3
temperature of the evaporator
fan.
Uses the residual cold from the
0
0
evaporator.
Delays the start of the evapo-
rator fan after defrosting or a
+5°C
-15°C
restart together with the delay
time.
Upper temperature point for
+35°C
+35°C
speed regulation. (See figure)
Lower temperature point for
0
0
speed regulation. (See figure)
Upper percentage for speed
80
80
regulation. (See figure)
Lower percentage for speed
0
0
regulation. (See figure)
Right reserved to make technical changes!
GB