Pentair Pool Products Nocchi R4TE Use And Maintenance Manual page 23

Table of Contents

Advertisement

Minimum
Parameter defining minimum motor rotation frequency.
frequency
INF F
Maximum
Parameter defining maximum motor rotation frequency.
frequency
SUP F
Reactivity factor
Parameter defining the speed with which the motor responds to
changes in pressure. The lower the setting the faster the motor's
response.
ANP F
Bottom scale
Parameter defining the sensor at the bottom of the scale. (in bar).
sensor
Depends on the type of sensor applied.
SUP S
Zero sensor
Minimum value read by the sensor (zero).
INF S
Use to enter an offset value for the pressure sensor. Depends on
Offset sensor
the type of sensor applied.
OFF P
Switching off time Interval of time during which pressure must remain stable (+/- 0.1
Bar) with a rotation lower than the average switching off frequency
+ 10 to trigger the motor shutdown cycle (seconds).
SPE T
Pressure
Subtract this figure from the set point to obtain pressure when the
threshold
motor is started-up. In other words, the motor starts-up when
pressure reaches the set point value minus the threshold value
(BAR).
DIF P
Water
alarm
Indicates minimum system pressure, a lack of water alarm will be
pressure
generated under this threshold value Set to zero to disable this
function.
ALL P
Page 21 of 22
21
21 - GB -
20
20
40
50
40
60
15
1
50
xx
1
30
0,6
0,1
10
x
0,0
99
10
3
30
0,3
0,1
0,5
0
0
1
51