Examples For Voltage Supply; Supply Line And Power Supply (M12) - Phoenix Contact Axioline E Series User Manual

System and installation
Table of Contents

Advertisement

UM EN AXL E SYS INST
40
PHOENIX CONTACT
4.8.3

Examples for voltage supply

NOTE: Damage to the electronics
The total current at U
must not exceed 12 A.
S
The total current at U
must not exceed 12 A.
A
DI16
BUS IN
BUS
X21
U
PWR IN
PWR OUT
S
U
A
X31
X01
X03
X05
X07
Figure 4-19
Example for the supply and forwarding of supply voltages
4.8.4

Supply line and power supply (M12)

For M12 connectors in Axioline E devices, a maximum of 12 A per contact is permitted.
To ensure that this condition is met, the following factors must be considered:
1.
Current consumption of the Axioline E devices (see data sheets)
2.
Current consumption of the connected sensors
3.
Current consumption of the connected actuators
4.
Length of the cables and losses on these cables
It is particularly important that these factors are observed when forwarding the supply
voltage.
DI8 DO4 2A
BUS IN
BUS OUT
X21
X22
PWR IN
X31
X32
X01
X02
X03
X04
X05
X06
X07
X08
DI8 DO8
BUS OUT
BUS IN
X22
X21
PWR OUT
PWR IN
X32
X31
X02
X01
X04
X03
X06
X05
X08
X07
BUS OUT
X22
PWR OUT
X32
X02
X04
X06
X08
8395_en_03