Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
†.
The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG,
the unit will deliver less CFM
‡.
Add these resistance values to the available static resistance in the respective Blower Performance Table.
TABLE 7: MOTOR AND DRIVE DATA- BELT-DRIVE BLOWER
BLOWER
MODEL
RANGE
HP
(RPM)
DHG 036
790 - 1,120
1-1/2
DHG 048
790 - 1,120
1-1/2
DHG 060
850 - 1,220
1-1/2
*.
All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air,
heating device
upstream of any
TABLE 8: ELECTRICAL DATA- BASIC UNIT
VOLTAGE LIMITATIONS
POWER
(SEE NOTE 1)
MODEL
SUPPLY
DHG
MIN.
208/230-3-60
187
036
460-3-60
414
208/230-3-60
187
048
460-3-60
414
060
208/230-3-60
187
460-3-60
414
Note: 1. Rated in accordance with ARI Standard 110, utilization range "A". 2. Dual Element, time delay type. 3. Based on 75º copper conductors.