Static Resistances; Motor And Drive Data- Belt-Drive Blower; Electrical Data- Basic Unit - York SUNLINE ULTRA D1HE 036 Installation Manual

Electric / electric single package air conditioners
Table of Contents

Advertisement

TABLE 5: STATIC RESISTANCES
DESCRIPTION
* †
Economizer
1
Electric Heaters
*
Bottom Duct Connections
Cooling Only
*.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
†.
The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG,
the unit will deliver less CFM
‡.
Add these resistance values to the available static resistance in the respective Blower Performance Table.
TABLE 6: MOTOR AND DRIVE DATA- BELT-DRIVE BLOWER
BLOWER
MODEL
RANGE
HP
(RPM)
DHE036
790 - 1,120
1-1/2
DHE048
790 - 1,120
1-1/2
DHE060
850 - 1,220
1-1/2
*.
All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air,
heating device
upstream of any
TABLE 7: ELECTRICAL DATA- BASIC UNIT
VOLTAGE LIMITATIONS
MODEL
POWER
DHE
SUPPLY
208/230-3-60
036
460-3-60
208/230-3-60
048
460-3-60
060
208/230-3-60
460-3-60
Note: 1. Rated in accordance with ARI Standard 110, utilization range "A". 2. Dual Element, time delay type. 3. Based on 75º copper conductors.
14
EXTERNAL STATIC PRESSURE DROP
1000
5 - 15 KW
20 - 30 KW
*
MOTOR
RPM
FRAME
SERVICE
SIZE
FACTOR
1,725
56
1.15
1,725
56
1.15
1,725
56
1.15
COMPRESSOR
(SEE NOTE 1)
MIN.
MAX.
RLA
187
253
14.1
414
504
7.1
187
253
10.0
414
504
5.2
187
253
16.0
414
504
8.3
1200
1400
1600
1800
0.07
0.08
0.09
0.11
0.13
0.04
0.05
0.06
0.07
0.08
0.06
0.07
0.08
0.09
0.11
0.06
0.07
0.08
0.09
0.10
0.08
0.10
0.12
0.14
0.16
ADJUSTABLE
MOTOR PULLEY
BLOWER PULLEY
PITCH
BORE
PITCH DIA. (IN.)
DIA. (IN.)
2.4 - 3.4
7/8
5.7
2.4 - 3.4
7/8
5.7
2.4 - 3.4
7/8
5.2
COND.
SUPPLY
FAN
AIR
MOTOR,
BLOWER
FLA
MOTOR,
FLA
LRA
FLA
110.0
2.3
5.3
54.0
1.4
3.1
110.0
2.3
5.2
54.0
1.4
2.6
137.0
2.3
6.0
69.0
1.4
3.0
035-13329-001-B-0504
RESISTANCE, IWG
CFM
2000
2200
2400
2600
0.15
0.17
0.20
0.23
0.10
0.12
0.14
0.16
0.13
0.15
0.17
0.20
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.26
FIXED
BORE
PITCH
LENGTH
1
37.3
1
37.3
1
37.3
TOTAL UNIT
MAX. FUSE
AMPACITY
SIZE (SEE
AMPS
NOTE 2) AMPS
25.2
35
13.3
20
23.9
35
12.4
15
28.3
40
14.8
20
Unitary Products Group
2800
3000
0.26
0.30
0.19
0.22
0.23
0.26
0.19
0.22
0.29
0.32
BELT
DESIGNATIONS-
A36
A36
A36
MAX HACR
BREAKER
SIZE AMPS
35
20
35
15
40
20