Phasing; Static Resistances - York DM036 Installation Manual

R-410a 3 - 6.3 ton 50 hertz
Hide thumbs Also See for DM036:
Table of Contents

Advertisement

5011492-XIM-B-0815
Table 21: Belt Drive Motor And Drive Data
BLOWER
MODEL
RANGE (RPM)
HP RPM
5 TON
812-1102
1.5 1450
6 TON
948-1227
1.5 1450
1. All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they
are located in the moving air, upstream of any heating device.
Table 22: Static Resistances
DESCRIPTION
1,2
ECONOMIZER
7-15KW
1
ELECTRIC HEATERS
20-30KW
BOTTOM DUCT CONNECTIONS
3
COOLING ONLY
DESCRIPTION
1,2
ECONOMIZER
7-15KW
1
ELECTRIC HEATERS
20-30KW
BOTTOM DUCT CONNECTIONS
3
COOLING ONLY
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
system is less than 62.0 Pa [0.25 IWG], the unit will deliver less M3/S or CFM during full economizer operation.
3. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.

Phasing

YORK MODEL DM units are properly phased at the factory.
Check for proper compressor rotation. If the blower or
compressors rotate in the wrong direction at start-up, the
electrical connection to the unit is misphased. Change the
incoming line connection phasing to obtain proper rotation.
(Scroll compressors operate in only one direction. If the scroll is
drawing low amperage, has similar suction and discharge
pressures, or producing a high noise level, the scroll is
misphased).
34
1
MOTOR
ADJUSTABLE MOTOR PULLY
FRAME
SERVICE
DESIG-
SIZE
FACTOR
NATION
56
1.0
IVL44
56
1.0
IVM50
0.47
0.57
0.66
17.4
19.8
22.3
10.0
12.4
14.9
14.9
17.4
19.8
1
14.9
17.4
19.8
19.8
25.0
29.8
1000
1200
1400
0.07
0.08
0.09
0.04
0.05
0.06
0.06
0.07
0.08
1
0.06
0.07
0.08
0.08
0.10
0.12
PITCH DIA.
BORE
mm
inch
mm
inch
69-97
2.8-3.8
22
7/8
86-112
3.4-4.4
22
7/8
RESISTANCE, Pa
3
M
0.75
0.85
0.94
27.3
32.2
37.2
17.4
19.8
24.8
22.3
27.3
32.2
22.3
24.8
27.3
34.7
39.7
44.6
RESISTANCE, IWG
CFM
1600
1800
2000
0.11
0.13
0.15
0.07
0.08
0.10
0.09
0.11
0.13
0.09
0.10
0.11
0.14
0.16
0.18
Scroll compressors require proper rotation to operate
correctly. Units are properly phased at the factory. Do
not change the internal wiring to make the blower,
condenser fans, or compressor rotate correctly.
FIXED BLOWER PULLY
PITCH DIA.
BORE
mm
inch
mm inch
127
5.0
25
1
132
5.2
25
1
/S
1.03
1.13
1.23
42.2
49.6
57.0
29.8
34.7
39.7
37.2
42.2
49.6
29.8
34.7
39.7
49.6
57.0
64.5
2200
2400
2600
0.17
0.20
0.23
0.12
0.14
0.16
0.15
0.17
0.20
0.12
0.14
0.16
0.20
0.23
0.26
Johnson Controls Unitary Products
BELT
PITCH
DESIG-
LENGTH
NATION
mm
inch
922
36.3
A35
947
37.3
A36
1.32
1.42
64.5
74.4
47.1
54.6
57.0
64.5
47.1
54.6
71.9
79.4
2800
3000
0.26
0.30
0.19
0.22
0.23
0.26
0.19
0.22
0.29
0.32