York D1EB036 Installation Manual

York D1EB036 Installation Manual

Champion series single package air conditioners electric/electric, air-cooled
Hide thumbs Also See for D1EB036:

Advertisement

INSTALLATION
MANUAL - 50 HZ
CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . 14
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
See following pages for a complete Table of Contents.
NOTES, CAUTIONS AND WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes are intended to
clarify or make the installation easier. Cautions are given to
prevent equipment damage. Warnings are given to alert
installer that personal injury and/or equipment damage may
result if installation procedure is not handled properly.
CAUTION:
READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
CHAMPION
SINGLE PACKAGE AIR CONDITIONERS
ELECTRIC/ELECTRIC, AIR-COOLED
MODELS: D1EB036, 048 DIRECT DRIVE
D1EB060 BELT DRIVE
(WORLD 50 HZ)
Tested in accordance with:
®
SERIES
ISO 9001
Certified Quality
Management System
173858-YIM-A-0306

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D1EB036 and is the answer not in the manual?

Questions and answers

Summary of Contents for York D1EB036

  • Page 1 READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT. SAVE THIS MANUAL ® CHAMPION SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED MODELS: D1EB036, 048 DIRECT DRIVE D1EB060 BELT DRIVE (WORLD 50 HZ) Tested in accordance with: ISO 9001 Certified Quality Management System 173858-YIM-A-0306...
  • Page 2: Table Of Contents

    5 ADDITIONAL STATIC RESISTANCE ....9 6 D1EB036 SUPERHEAT CHARGING (IMPERIAL) . . . 10 7 D1EB036 SUPERHEAT CHARGING (METRIC) ..10 8 D1EB048 SUPERHEAT CHARGING (IMPERIAL) . . . 11 9 D1EB048 SUPERHEAT CHARGING (METRIC) .
  • Page 3: General

    If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should PRODUCT CATEGORY D = Single Package Air Conditioner (Air Cooled) PRODUCT GENERATION 1 = NEW or Current Design...
  • Page 4: Rigging Or Handling

    should meet local codes and unit weight. Do not tie the slab to the building foundation. For roof top installation, be sure the structure will support the weight of the unit plus any field installed components. Unit must be installed on a level roof curb or appropriate angle iron frame providing adequate support under the compressor/condenser section.
  • Page 5: Filters

    173858-YIM-A-0306 Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D. A closed return duct system shall be used. This shall not pre- clude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to min- imize the transmission of noise.
  • Page 6: Physical Data

    TABLE 3: PHYSICAL DATA COMPONENT NOMINAL TONNAGE COOLING PERFORMANCE RATING Indoor DB/WB °C Outdoor DB/WB °C Total Output (MBH) Total Output kW (MBH) Total Input kW COP² Refrigerant charge kg (lb) Refrigerant type DIMENSIONS (inches) Length mm (in.) Width mm (in.) Height mm (in.) OPERATING WT.
  • Page 7: Power And Control Wiring

    173858-YIM-A-0306 POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the cur- rent N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordi- nances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the com- pressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 3.
  • Page 8: Checking Supply Air Cfm

    TABLE 4: ELECTRICAL DATA SIZE MODEL POWER (TONS) 380/415-3-50 (3.0) 380/415-3-50 (4.0) 380/415-3-50 (5.0) Minimum Circuit Ampacity. Maximum Over Current Protection per standard UL 1995. Fuse or HACR circuit breaker size installed at factory or field installed. CHECKING SUPPLY AIR CFM To check the supply air CFM after the initial balancing has been completed: Remove the two ¼...
  • Page 9: Additional Static Resistance

    173858-YIM-A-0306 TABLE 5: ADDITIONAL STATIC RESISTANCE Size Airflow Model (Tons) /s (cfm) 0.42 (900) 0.47 (1000) 0.52 (1100) 0.57 (1200) (3.0) 0.61 (1300) 0.66 (1400) 0.71 (1500) 0.57 (1200) 0.61 (1300) 0.66 (1400) 0.71 (1500) 0.76 (1600) (4.0) 0.80 (1700) 0.85 (1800) 0.90 (1900) 0.94 (2000)
  • Page 10: D1Eb036 Superheat Charging (Imperial)

    TABLE 6: D1EB036 SUPERHEAT CHARGING (IMPERIAL) OUTDOOR TEMPERATURE (°F) 21.1 21.6 19.5 20.0 17.9 18.5 16.3 16.9 14.7 15.3 13.1 13.8 11.5 12.2 TABLE 7: D1EB036 SUPERHEAT CHARGING (METRIC) OUTDOOR TEMPERATURE (°C) 11.7 10.8 SUPERHEAT AT COMPRESSOR SUCTION (°F) AIRFLOW = 1,300 CFM INDOOR WB TEMPERATURE (°F)
  • Page 11: D1Eb048 Superheat Charging (Imperial)

    173858-YIM-A-0306 TABLE 8: D1EB048 SUPERHEAT CHARGING (IMPERIAL) OUTDOOR TEMPERATURE (°F) 19.9 16.5 13.1 TABLE 9: D1EB048 SUPERHEAT CHARGING (METRIC) OUTDOOR TEMPERATURE (°C) 11.0 Unitary Products Group SUPERHEAT AT COMPRESSOR SUCTION (°F) AIRFLOW = 1,800 CFM INDOOR WB TEMPERATURE (°F) 21.0 22.1 23.3 24.4...
  • Page 12: D1Eb060 Superheat Charging (Imperial)

    TABLE 10: D1EB060 SUPERHEAT CHARGING (IMPERIAL) OUTDOOR TEMPERATURE (°F) 21.9 16.0 10.1 TABLE 11: D1EB060 SUPERHEAT CHARGING (METRIC) OUTDOOR TEMPERATURE (°C) 12.2 SUPERHEAT AT COMPRESSOR SUCTION (°F) AIRFLOW = 2,000 CFM INDOOR WB TEMPERATURE (°F) 23.8 25.7 27.6 29.4 18.4 20.7 23.0 25.3...
  • Page 13: Unit Dimensions

    173858-YIM-A-0306 FIGURE 5 - UNIT DIMENSIONS Unitary Products Group...
  • Page 14: Yim-A

    SEQUENCE OF OPERATION COOLING The following sequences of operation are based on using a standard single-stage cooling thermostat. WITH POWER TO UNIT AND THERMOSTAT IN COOLING MODE If the fan switch on the thermostat is in the “ON” position, the 24 volts at “G” will energize the “K1" relay on the fan control board, close the ”K1"...
  • Page 15: Typical Wiring Diagram 3 & 4 Ton (380/415-3-50 Power Supply)

    173858-YIM-A-0306 FIGURE 3 - TYPICAL WIRING DIAGRAM 3 & 4 TON (380/415-3-50 POWER SUPPLY) Unitary Products Group...
  • Page 16: Typical Wiring Diagram 5 Ton (380/415-3-50 Power Supply)

    173858-YIM-A-0306 FIGURE 4 - TYPICAL WIRING DIAGRAM 5 TON (380/415-3-50 POWER SUPPLY) Unitary Products Group...
  • Page 17: Typical Wiring Diagram Legend

    173858-YIM-A-0306 FIGURE 5 - TYPICAL WIRING DIAGRAM LEGEND ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SER- VICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DAN- GEROUS OPERATION.
  • Page 18 173858-YIM-A-0306 Unitary Products Group...
  • Page 19 173858-YIM-A-0306 Unitary Products Group...
  • Page 20 Subject to change without notice. Printed in U.S.A. Copyright © 2006 by Unitary Products Group. All rights reserved. Unitary Products Group 5005 York Drive 173858-YIM-A-0306 Supersedes: Nothing Norman 73069...

This manual is also suitable for:

D1eb060D1eb048